Technical data
Page 19
Page __________ of __________
Location/Installation
Models RIH/RIHV - High Intensity Infrared Heaters
INSTRUCTIONS:
1. Hang full length chains at
desired height and attach
to back of heater (C) with
S-hooks.
2. Attach one end of the 1’
length chains with S-hooks
to front of heater (D).
3. Place other end of chains
with S-hooks in loop (B) on
the full length chain.
4. Check degree of angle
mounting. Adjust degree
of mounting angle by mov-
ing “S” hooks at point B.
5. Check to be sure unit is
level. Crimp all “S” hooks
closed.
Sample Specifications
Models RIH/RIHV - High Intensity Infrared Heaters
Provide gas-fired, high-intensity infrared heaters manufactured as Reznor brand units. The heaters shall be equipped for use
with natural (propane) gas to operate on a 115 volt supply voltage.
The burner control system shall have a direct spark ignition with 100% safety shut-off and a solenoid gas valve with 1/2” NPT
inlet.
Heaters shall be of compact modular design and rugged construction consisting of the controls; a seamless aluminized steel
plenum chamber with stainless steel ceramic tile retainer clips; surface combustion ceramic burner capable of full intensity
temperature in less than 30 seconds; venturi mixer of spun metal construction for precision metering of air/gas mixture; highly
polished aluminum reflector; and balanced suspension holes.
The burner assembly shall be removable with a single screw for cleaning or replacement. The ceramic combustion surface
shall reach temperatures up to 1850°F and be of a cordierite-based grooved design with alternating rows of precision
perforations producing a shorter stable flame.
These units must be approved for installation in The United States and Canada by the Canadian Standards Association (CSA).
(Capacities, dimensions, and additional field-installed options as described in this catalog.)
B
C
D
S
A
#5 S Hook (Typ)
1 Foot / 0.3 meter
Length Chain
with S-Hooks
Degree of
Angle Mounting
Adjust Length to
Change Mounting
Angle