Technical data

0803UDSA-2GBEN, Pag. 6/36
Clearances (mm)
Units must be installed so that the minimum clearances in the following table are
provided for combustion air space, inspection and service and for proper spacing from
combustible materials.
Attention :
The clearance distance from the flue system must be minimum 150mm at all points !
Combustion air
supply and flue
system diameters
Diameter gas
connection
Table 2 : Clearances (mm)
Table 3 :
(*) : Heaters can be base mounted on suitable non combustible supports.
Model X Y Z (*) U V
008-2
Æ
030-2 450 50 50 50 850
035-2
Æ
100-2 450 100 100 100 850
Model 008-2 011-2 015-2 020-2 025-2 030-2 035-2 043-2 050-2 055-2 064-2 073-2 085-2 100-2
Ø flue/ air inlet
(mm)
80 80 80 80 100 100 100 100 100 130 130 130 130 130
Ø gas con-
nection
1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"