Technical data
0803UDSA-2GBEN, Pag. 21/36
Figure 10b : HONEYWELL gas valve (type 035-2 -> 100-2)
Table 8 : Burner jets and pressures
2
6
3
1
4
57
8
Legend
1) Gas inlet
2) Gas outlet
3) Inlet pressure tap
4) Outlet pressure tap
5) 6.3mm AMP terminals and screws for wiring
6) 6.3mm AMP terminals
7) Earth terminal/screw (line voltage models only)
8) Pressure regulator adjustment screw
Minimum inlet pressure natural gas G20 : 16,6mbar
Minimum inlet pressure propane gas G31 : 35,2mbar
008-2 011-2 015-2 020-2 025-2 030-2 035-2 043-2 050-2 055-2 064-2 073-2 085-2 100-2
Burner jet dia 2,60 3,20 3,70 4,20 4,80 5,30 5,75 6,50 6,80 7,10 8,00 7,40 8,90 10,00
Burner
pressure
mbar 8,00 7,90 7,80 7,10 8,20 7,50 7,90 7,10 7,90 8,40 7,90 12,00 8,00 7,10
inlet pressure
20mbar
Burner jet dia 1,40 1,70 1,95 2,15 2,60 2,80 3,10 3,35 3,70 3,90 4,15 4,50 4,90 5,20
Burner
pressure
mbar 36,90 36,90 36,90 36,90 36,80 36,80 36,00 35,90 35,80 35,70 35,60 35,10 34,60 34,50
inlet pressure
37 mbar
Nat. Gas
(G20)
Prop.
(G31)