Technical data
0803UDSA-2GBEN, Pag. 13/36
9. Hanging
the heater
Warning : Do not place or add additional weight to the suspended heater.
Before suspending the heater, check the supporting structure to verify that it has
sufficient load-carrying capacity to support the weight of the unit.
WARNING:
Check the supporting
structure to verify that it
has sufficient load-
carrying capacity to
support the unit weight.
Suspend the heater only
from the threaded nut
retainers or with a
manufacturer provided kit.
DO NOT suspend from the
heater cabinet panels. .
Be sure that the threaded hanger rods are locked to the heater as illustrated in
figure 6. Recommended maximum hanger rod length is 1.8m. Where longer drops
are required, ensure that restraints are fitted to prevent excess lateral movement
and supports are adequately sized.
Leave the unit on the pallet. If the bottom of the unit is not supported or protected
damage can occur.
Figure 6 : Suspending the heater with rods from the threaded nut retainers
Add a nut to lock the M10x1.5
hanger rod to the heater
Table 6 : weights (kg)
The heater is supplied with four point suspension. All points must be used. Two
threaded nut retainers are provided on each side of the top of the heater. See figure
6 for hanger rod size.
Detail
Size 008-2 011-2 015-2 020-2 025-2 030-2 035-2 043-2 050-2 055-2 064-2 073-2 085-2 100-2
kg 30 33 38 40 56 60 88 99 99 112 118 143 158 168