Replacement Limit Controls

Form P-FAN&LIMIT, P/N 147678 R3, Page 5
NOTES for TABLE 2:
IMPORTANT: Always verify temperature setting of the original control.
A
For installing functional replacement Fan Relay Kit, P/N 63254, follow the instructions on page 7. NOTE: When
inventory of components in relay kit are depleted, replacement will no longer be available.
B
Models FE and BE and Models B and F with spark pilot manufactured after 9/99 (Serial No. Date Code AYJ) do not
have an ECO limit control.
C
P/N 209184 is a relay kit to replace discontinued fan control P/N 10357. Kit includes instructions.
D
Replacement kit with spring-loaded fan control assembly. To install, follow the instructions on page 6.
E
Furnace next to the blower.
F
Second furnace from the blower
G
Third furnace from the blower.
Model Size Fan Control Replaces Limit Control Replaces
(H), (C), (HC) - X, XE prior to
Series 6
All
C
209184 10357 50418 (145°F), auto, blue
XA, XB, XC, XD, XJ, XR All
C
209184 10357 50418 (145°F), auto, blue
XL 30-400
D
147676 (135°F)
48706
(150°F),
63555
(150°F),
93629
(150°F)
45602 (180°F), auto
CXL 140-400
XLB 30, 45
D
147677 (150°F) 45602 (180°F), auto
CXLB 30-105
CXL 30-105
D
147676 (135ºF) 85449 (200°F)
XLB 60-105, 300-400
D
147677 (150ºF) 82091 (160°F)
CXLB 300-400
XLB, CXLB 200-225
D
147677 (150ºF)
45602 (180°F)
XLB, CXLB 125-170 85449 (200°F)
XLB, CXLB 250 82091 (160°F)
ECO Limit Control for XL, CXL,
XLB, CXLB - Starting 4/83 (Serial
No. AID)
All Sizes; Standing
Pilot only
82414 (306°F)