NG to LP Conversion Guide

Form CP-UD-GC, P/N 197209R11, page 3







































FIGURE1-GasValveandBurnerOriceLocations(Fan model is illustrated; gas valve and orice
locations are the same on blower models.)
4.SelectandInstalltheBurnerOrice-AppliestoModelsUDAP/UDAS/UDBP/
UDBS - All Sizes
Remove or Install the Air Restrictor Plate - Applies only to Models UDAP/
UDAS/UDBP/UDBS - Sizes 30, 45, 60, 75, 100, and 150 AND Models UDBP/
UDBS Size 125
WARNING
Donotattempttodrillorice.Usefactory-suppliedoriceonly.
4A) SelecttheoriceandDetermineAirRestrictorPlateRequirement.
Because each kit is designed to convert more than one size of heater, there are
two or three burner orices per kit. From TABLE 1 below, nd the marking that
is on the orice for the size of heater being converted. From the kit, select the
orice with that marking. The other orice(s) will not be used in this conversion.
BurnerOrice-ModelsUDAP,UDAS,UDBP,andUDBS
Size 30 45 60 75 100 125
Natural
Gas
P/N 196853 196838 196839 196855 120158 196840
Marking #37 #30 3.7MM #19 #10 #4
Propane
P/N 196844 196845 196846 196852 196854 196847
Marking 1.6MM #48 2.3MM #39 3.0MM 3.2MM
Size 150 175 200 225 250 300 350 400
Natural
Gas
P/N 131581 196891 196892 221121 208255 221122 221123 196897
Marking 5.9MM E 6.8MM 6.95MM L 8.0MM 8.7MM 9.6MM
Propane
P/N 196898 196899 196900 196901 196902 196903 196904 196905
Marking 9/64" #24 4.1MM 11/64" #14 #8 #3 5.8MM
TABLE 1 - Burner
OriceP/N’sand
Markings