UDAP/APD/UDBP Venting Requirements

Form I-UD&APD Series-V-PV (5-17), P/N 195675R20, Page 1
APPLIES TO:
Standard Power Vent, Fan Type Unit Heaters:
Model UDAP & Model APD
Standard Power Vent, Blower Type Unit Heaters:
Model UDBP
Form I-UD&APD Series-V-PV (05-17)
Obsoletes I-UD&APD Series-V-PV (03-17)
General
WARNING
Each heater requires its own individual vent pipe run and
vent cap. Manifolding of vent runs can cause recirculation
of combustion products into the building. Failure to comply
could result in severe personal injury or death and/or
property damage.
WARNING
Installation should be done by a qualied agency in
accordance with these instructions. The qualied service
agency installing this heater is responsible for the
installation.
This manual applies only to venting instructions and must be used with the installation
manual. Both manuals are shipped with the heater. If either manual is missing, contact
your distributor before beginning installation. The instructions in this manual apply to
Standard Power Vent fan type and Standard Power Vent blower type unit heaters.
Verify that the label near the vent outlet on the heater matches the label illustrated
below. (Label P/N is 201214; color is red.)
POWER
VENT
201214
Rear View of a Std Power Vent Fan Type Unit Heater
CAUTION: Standard Power Vent Fan & Blower type unit heaters
should not be used in an application where the heated space
temperature is below 50°F (10°C). Operating under low ambient
conditions may cause condensate to form in the heat exchanger.
Venting Requirements for Indoor, Power Vent