S5BP SERIES 11.2 EER USER’S MANUAL / INSTALLATION INSTRUCTIONS R410A SPLIT SYSTEM AIR CONDITIONER - 3 PHASE IMPORTANT Please read this information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit. Keep this literature where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your servicing contractor.
USER INFORMATION Important Safety Information ....................................4 Operating Instructions ...............................................4 Cooling Operation .....................................................4 Heating Operation .....................................................4 Operating the Air Conditioner for Automatic Cooling and Heating ..................................................4 Operating the Indoor Blower Continuously ................4 Turning the Air Conditioner Off ...
USER INFORMATION IMPORTANT SAFETY INFORMATION Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
INSTALLER INFORMATION IMPORTANT SAFETY INFORMATION Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death.
AIR CONDITIONER INSTALLATION General Information The S5BP series air conditioner is designed only for outdoor rooftop or ground level installations. This unit has been tested for capacity and efficiency in accordance with A.R.I. Standards and will provide many years of safe and dependable comfort, providing it is properly installed and maintained. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards.
Ground Level Ground level installations must be located according to local building codes or ordinances and these requirements: • Clearances must be in accordance with those shown in Figure 2 (page 6). • A suitable mounting pad (Figure 3) must be provided and be separate from the building foundation. The pad must be level and strong enough to support the unit’s weight. The slab height must be a minimum of 2” (5 cm) above grade and with adequate drainage.
ELECTRICAL WIRING WARNING: To avoid risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply. Label all wires prior to disconnection when servicing the unit.
Unbalanced 3-Phase Supply Voltage Voltage unbalance occurs when the voltages of all phases of a 3-phase power supply are no longer equal. This unbalance reduces motor efficiency and performance. Some underlying causes of voltage unbalance may include: Lack of symmetry in transmission lines, large single-phase loads, and unbalanced or overloaded transformers. A motor should never be operated when a phase imbalance in supply is greater than 2%.
START UP & ADJUSTMENTS Pre-Start Check List Verify the indoor unit is level and allows proper condensate drainage. Verify the outdoor coil and top of the unit are free from obstructions and debris, and all equipment access/ control panels are in place. Verify that the duct work is sealed to prevent air leakage. Verify that the line voltage power leads are securely connected and the unit is properly grounded.
After refrigerant line connections are completed, it is required that you leak check and evacuate the indoor section and all line connections (using proper methods) before finalizing the full system refrigerant charge. For final charges based on matched systems and specified line lengths, see physical and electrical specifications (Table 4, page 13).
COMPONENT FUNCTIONS Anti-Short Cycle Timer (ASCT) A protective short cycle timer is factory installed and located in the control panel of the outdoor section. If power to the compressor low voltage control circuit is interrupted, the outdoor unit will not energize for approximately 5 minutes. High Pressure Switch (HPS) A high-pressure switch is factory-installed and located in the liquid line internal to the outdoor unit.
ELECTRICAL INFORMATION Model Number S5BP- 090C 090D 120C 208-230V 460V 208-230V 120D 460V 920888 920889 920890 920891 PERFORMANCE DATA Gross Cooling Capacity (95oF) Btuh 92,400 92,400 121,700 121,700 1 Net Cooling Capacity - Btuh 90,000 90,000 117,000 117,000 1 A.R.I. Rated Airflow - C.F.M. 3,000 3,000 4,000 4,000 2 Cooling - Efficiency E.E.R. (Btu/Watt) 11.70 11.70 11.20 11.20 3 Cooling - Efficiency I.E.E.R. 11.80 11.80 11.50 11.
FIELD WIRING LOW VOLTAGE HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE HIGH VOLTAGE Y R S C L2 L1 CAS CC T2 T3 CCH ASCT C L3 CC ASCT ANTI SHORT CYCLE TIMER CC COMPRESSOR CONTACTOR CAS CONTACTOR AUXILLIARY SWITCH (1NO/1NC) CCH COMPRESSOR CRANKCASE HEATER HPS HIGH PRESSURE SWITCH WITH AUTO RESET LPS LOW PRESSURE SWITCH CC ASCT 24V COMPRESSOR T1 L3 L2 THREE PHASE OUTDOOR FAN MOTOR HIGH LOW PRESSURE PRESSURE SWITCH SWITCH SINGLE PHASE OUTDOOR FAN MOTOR CC LEGEND: R L1 T3 CCH L3 L2
NOTE: C &W2 to be connected to electric heat.
S5BP CHARGING CHARTS - COOLING ONLY Application Notes on the Use of Charging Charts • This equipment’s cooling system contains refrigerant under high pressure. Always use safe and environmentally sound methods when handling refrigerant handling or servicing the unit. Review the factory literature and safety warnings prior to servicing. • When repairing system leakages, always use a nitrogen (inert) gas to protect the refrigerant system and pressure check the repair before re-charging.
S5BP Charging Chart - Cooling 7.5 Ton Split System A.C. w/ B5SM-090* Indoor Air Handler 525 500 475 Remove refrigerant when above curve Liquid Pressure (psig) 450 425 400 375 350 325 300 275 250 225 Add refrigerant when below curve 200 175 55 60 65 70 75 80 85 90 95 100 Liquid Temperature (° F) 105 110 115 120 125 Figure 8. Charging Chart for 7.
INSTALLATION/PERFORMANCE CHECK LIST REFRIGERATION SYSTEM: INSTALLATION ADDRESS: Was unit given 24 hr warm up period for crankcase heaters? CITY ________________________ YES NO STATE ________________ UNIT MODEL # ________________________________________ Stage-1 Liquid Pressure (high side) ________________________ UNIT SERIAL # _______________________________________ Stage-1 Suction Pressure (low side) ________________________ Unit Installed Minimum clearances per Figure 2 (page 6)? Has the owner’s