MG3P Installation Manual
40
Table 12. MG3P-108U1AAD1 (With 5-speed ECM motor)
HEATING AIRFLOW (CFM) & TEMPERATURE RISE (°F)
MODEL NAME/
HEATING INPUT
RETURN
AIR VIA:
MOTOR
SPEED
External Static Pressure (in. w.c.)
0.1 0.2 0.3 0.4 0.5
CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
MG3P-108U1AAD1
108,000 BTU/Hr
Bottom
5 - High*
4 - Med-High** 2,040 45 1,985 46 1,940 47 1,890 49 1,835 50
3 - Med-Low 1,845 50 1,795 51 1,735 53 1,685 55 1,635 56
2 - Alternate 1,665 55 1,600 58 1,545 60 1,480 62 1,430 64
1 - Low***
Side
5 - High*
4 - Med-High** 2,035 45 1,980 46 1,935 48 1,885 49 1,830 50
3 - Med-Low 1,830 50 1,775 52 1,730 53 1,665 55 1,615 57
2 - Alternate 1,665 55 1,610 57 1,555 59 1,500 61 1,445 64
1 - Low***
Side + Bottom
or 2 sides
5 - High*
4 - Med-High** 2,050 45 1,995 46 1,950 47 1,890 49 1,840 50
3 - Med-Low 1,855 50 1,800 51 1,750 53 1,695 54 1,645 56
2 - Alternate 1,675 55 1,620 57 1,560 59 1,505 61 1,450 63
1 - Low***
COOLING AIRFLOW (CFM)
MODEL NAME/
HEATING INPUT
RETURN
AIR VIA:
MOTOR
SPEED
External Static Pressure (in. w.c.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM CFM CFM CFM CFM CFM CFM CFM
MG3P-108U1AAD1
108,000 BTU/Hr
Bottom
5 - High* 2,265 2,210 2,170 2,120 2,070 2,030 1,975 1,925
4 - Med-High** 2,040 1,985 1,940 1,890 1,835 1,785 1,735 1,690
3 - Med-Low 1,845 1,795 1,735 1,685 1,635 1,580 1,535 1,480
2 - Alternate 1,665 1,600 1,545 1,480 1,430 1,385 1,330 1,260
1 - Low*** 1,095 1,015 935 850 775 695 635 585
Side
5 - High* 2,250 2,195 2,145 2,100 2,050 2,005 1,940 1,885
4 - Med-High** 2,035 1,980 1,935 1,885 1,830 1,780 1,730 1,680
3 - Med-Low 1,830 1,775 1,730 1,665 1,615 1,560 1,510 1,460
2 - Alternate 1,665 1,610 1,555 1,500 1,445 1,385 1,330 1,280
1 - Low*** 1,095 1,000 920 835 745 665 605 550
Side + Bottom
or 2 sides
5 - High* 2,275 2,230 2,180 2,125 2,080 2,030 1,985 1,935
4 - Med-High** 2,050 1,995 1,950 1,890 1,840 1,790 1,745 1,700
3 - Med-Low 1,855 1,800 1,750 1,695 1,645 1,595 1,540 1,490
2 - Alternate 1,675 1,620 1,560 1,505 1,450 1,395 1,345 1,285
1 - Low*** 1,125 1,025 925 845 765 660 595 545
*NOTES:
1. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.
2. Data is shown without filter.
3. Temperature rises in the table are approximate. Actual temperature rises may vary.
4. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
5. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
6. Unit ships with (4) speeds pre-wired. Use of the fifth speed will require changing the appropriate wires at the motor connection. Consult the
wiring diagram for more information.
* Factory Set Cool
** Factory Set Heat
*** Factory Set Circulation