Datasheet
Output type
Relay contact, approval up to 30 V switching voltage (e.g. for
power supply of a router)
Maximum current load of the contact 2 A @ 30V DC (resistive load!)
Software integration of input and output
Via GPIOs and process image. Output is optionally switched by hardware watch-
dog.
Hardware watchdog functionality
Can be disabled by bridging the 4-pole screw-type terminal. Reset by toggling a
GPIO or alternatively a bit in the process image.
Hardware watchdog intervall Trigger after approx. 60 seconds without toggling the reset bit.
Compatible modules for system expansion
All RevPi IO modules and RevPi Gateway modules can be connected via the
PiBridge system bus.
All RevPi Con modules can be connected via the ConBridge system bus.
ESD protection 4 kV / 8 kV (according to EN61131-2 and IEC 61000-6-2)
EMI tests Passed (according to EN61131-2 and IEC 61000-6-2)
Surge/Burst tests Passed (according to EN61131-2 and IEC 61000-6-2)
Buer time RTC min. 24 h
Optical indicator 6 status LEDs (bi-color), two of them freely programmable
RoHS conformity Yes
CE conformity Yes
UL certication
Yes, UL-File-No. E494534
Note: The device may only be supplied from circuits that comply with Class 2 or
Safety Extra Low Voltage (SELV) according to Class 9.4 of UL 61010-1.
Technical Data
RevPi Connect S
Article No.: 100362 (8 GB version)
Article No.: 100363 (16 GB version)
Article No.: 100364 (32 GB version)
page 2/2Errors excepted and possible alterations without prior notice.
Version: EN 1.0
KUNBUS GmbH, Heerweg 15C, 73770 Denkendorf, Germany | Tel: +49 (0) 711 400 91 500 | Fax: +49 (0) 711 400 91 501 | Email: info@kunbus.com | Web: www.kunbus.com