Mercury 2 & Intuitive Mercury Mini-Pack Installation Guide
www.resourcedm.com
Setup through front buttons
Setup Function Menu (Common to all types)
Recommended set-up method
If you are not connecting to a network and want to set up the controller through the buttons we recommend you use the following order
from the function menu.
rtc. Real time clock (This will automatically synchronise on network systems)
a. Use the up or down buttons to scroll through the display until the display reads “rtc”
b. Press enter. The display will show “t-1”. press enter again
c. Scroll hours up or down (0 – 23) press enter
d. Use up button to select “t-2”, press enter
e. Scroll minutes up or down (0 – 59) press enter
f. Repeat for t-3 (seconds 0 – 59)
g. Repeat for t -4 (Days up to 31)
h. Repeat for t -5 (months up to 12)
i. Repeat for t -6 (Year up to 99)
j. Use up button to display “ESC”, press enter to display “rtc”
Time clock is now set
type. Set/view controller type
a. From the function menu scroll to select type, press enter
b. Use the up/down buttons to scroll through case/coldroom configuration types. (see configuration table on page 3)
c. Press enter.
d. Scroll to select “ESC”
e. Press enter
Controller type configuration is now set
Inp
The INP menu option is used to configure the controller to operate with either a 4–20mA or 0–10V input signal.
Set to 0 for 4 – 20mA input
Set to 1 for 0 – 10V Input
Display
Option
Explained in
Paragraph
Display
Option
Explained in
Paragraph
IO
View Inputs / Outputs and
States
Input / output table
nEt
Set/view network configuration
Network
Configuration
PArA
Set/View Parameters
Set view parameters
SoFt
View software version
Unit
Probe type and
Celsius/Fahrenheit option
Set View Unit
OFSt
Probe Offset
Probe Offset
inP
Sets 4-20mA or 0-10V
Input
test
Test Outputs
Test Outputs
tyPE
Set/View Controller Type
Set/view controller type
ESC
Exit Setup mode
rtc
Set/view Clock (rtc = Real
Time Clock)
Real Time Clock
ENTER
UP
DOWN
To enter setup mode, hold the Enter and Down
buttons together for approximately 3 seconds until
the message “Ent” appears on the display. Now
press the Enter button again to enter the function
menu. IO will be displayed. Scroll up or down to go
through the list.