User guide

Revision 1.5 Page 16 of 19
Ensure that all power is
switched off before
installing or maintaining
this product
Mercury 2 & Intuitive Mercury Mini-Pack Installation Guide
www.resourcedm.com
Specification
Warning: Relay 5 output has hazardous voltages (Supply input voltage potential)
This does not apply to the Intuitive Mercury controller
Mercury Mk2 Mini Pack Controller
PR0710-MPA
Intuitive Mercury Mini-Pack Controller
PR0750-MPA
Power requirements
Supply Voltage Range
100 - 240 Vac ±10%
100 - 240 Vac ±10%
Supply Frequency
50 - 60 Hz
50 - 60 Hz
Maximum supply current
5.2 Amps (when relay 5 is fully loaded)
2 Amps
Typical supply current
<1 Amp
<1 Amp
General
Operating temperature range
+5
0
C to +50
0
C
+5
0
C to +50
0
C
Storage temperature range
-20
0
C to +65
0
C
-20
0
C to +65
0
C
Environmental
Indoor use at altitudes up to 2000m, pollution
degree 1, installation category II. Voltage
fluctuations not to exceed ±10% of nominal
voltage.
Indoor use at altitudes up to 2000m, pollution
degree 1, installation category II. Voltage
fluctuations not to exceed ±10% of nominal
voltage.
Size
78mm (W) x 36mm (H) x 110mm (D)
157mm (W) x 67mm (H) x 120 (D)
Approx Weight
170 grams
500 grams
Safety
EN61010
EN61010
EMC
EN61326; 1997 +Amdt. A1; 1998
EN61326; 1997 +Amdt. A1; 1998
Ventilation
There is no requirement for forced cooling
ventilation
There is no requirement for forced cooling
ventilation
Class 2 Insulation
No protective Earth is required and none
should be fitted
No protective Earth is required and none should
be fitted
Supply Fuse
The host equipment must provide a suitable
external over-current protection device such
as: -
Fuse: 6.3A 240 Vac Antisurge (T) HRC
conforming to IEC 60127
Built in fuse holder, fuse 2A 240Vac Antisurge (T)
HRC conforming to IEC60127, 32 x 6.3mm
Or MCB
6A, 240 VAC Type C conforming to BS EN
60898
2A, 240 VAC Type C conforming to BS EN 60898
(Note: controller has integral 2A fuse)
Relay Fuse
Not Fitted
10A 240Vac Antisurge (T) HRC conforming to
IEC60127, 32 x 6.3mm
Relay Specification
Relays 1-4 Mechanical
Exclusive common
Max current
6A Resistive (CosØ = 1)
2A Inductive ( CosØ = 0.4)
.10A Resistive (CosØ = 1)
3A Inductive ( CosØ = 0.4)
Max voltage
250Vac, 30V dc
250Vac. 30V dc
Relay Fuse
N/A
10A 240Vac Antisurge (T) HRC conforming to
IEC60127, 32 x 6.3mm
Relay 5 Mechanical Type (M)
Common connected to supply
live
Relay 5 Mechanical Type (M)
Exclusive common
Max current
3A (non inductive), COS=0.4 2A (inductive
load) 200,000 operations
10A Resistive (CosØ = 1)
3A Inductive ( CosØ = 0.4)
Max voltage
250Vac (Internal supply)
250Vac. 30V dc (external supply)
For compliance with the LVD, relays 3, 4 and 5
commons must be at the same potential as the
supply voltage
All relays are independent and can operate at
different potentials to the supply voltage.
!