Mercury 2 & Intuitive Mercury Mini-Pack Installation Guide
www.resourcedm.com
Probe Offset
This feature allows each probe value to be modified by an “offset” to take into account long cable runs. Offset values are from -10
O
C (-
18
O
F) to +10
O
C (+18
O
F) and on a channel basis. Example C1 = Probe 1.
Test Relay Outputs
Selecting the “tESt” option from display software menu allows for the relay outputs to be tested.
It can also be used to reset a compressor that has been locked out after a “Run Fail” by selecting the relay and forcing it on and then off
again. This renters the compressor back into the control algorithm for selection. See Run Proof for further information.
Remote Commands
The following commands can be used by a Data Builder program: -
Command
Value to send
Description
Optimisation
0
1
2
3
4
Stay
Zero
Up
Down
None
Haccp Command
0
1
2
HACCP LED OFF
HACCP LED On
HACCP LED Flashes
Button Command
0
1
2
Buttons backlights Off
Buttons backlights On
Buttons Backlights Flash
Use an “Analogue Out” block configured to the
controller name and in the value field type in the
command you require. Use a “Setting block” as
the input to the “Analogue Out” block to send the
Value.
See Example on the right, which turns on the
HACCP LED.