User guide

Revision 1.5 Page 12 of 19
Ensure that all power is
switched off before
installing or maintaining
this product
Mercury 2 & Intuitive Mercury Mini-Pack Installation Guide
www.resourcedm.com
Network Configuration
The final section to setup is the network address. In all instances, this must be done before the controller is plugged into the site network.
The controllers have an auto-initialise function, which will automatically log the device onto the site network. If the wrong address has
been entered onto the network, you will have to reset the controller address by setting the address to 00-0, and then re-enter the correct
address. (You may have to deregister the wrong address from the home system as well).
To set the controller onto a network you must first connect the controller to a communications module. This is either a: -
485 Legacy, or
IP Futura
Mercury Switch
485 Legacy module
485 legacy support the following protocol: -
Genus
Connecting a 485 legacy module to the controller will govern which set up screens are made available.
Display
Option
485t
485 Network Type
485A
485 Address/Name
gAdd *
Show underlying network address assigned to
Controller
rLog *
Re-log the controller back onto the network
CLrA *
Clear the address/name from the controller
ESC
Exit network menu. N.B. this option must be selected to save any changes
made in this menu
* These options are only available when the network type is set to Genus compatible.
The 485t option shows a value representing the network type. The possible values are:
Value
Network Type
1
Genus compatible (all versions)
The 485A option shows a value representing either the name of the controller in a Genus compatible network.
The value shown is of the form 05-6. This means the controller would try to log onto a Genus compatible network using the name
‘RC05-6’.
The following options are also available when the network type is set to Genus compatible.
The gAdd option displays (in hexadecimal format) the underlying network address assigned to the controller when it was logged onto the
network.
The rLog option allows the controller to be logged back onto the network with its current name. The ‘rLog’ message will flash for
confirmation. Press the Enter button to execute the command, Up or Down buttons to cancel.
Fast Network Address Reset
The CLrA option will clear out the network address and name in the controller. The ‘ClrA’ message will flash for confirmation. Press the
Enter button to execute the command, Up or Down buttons to cancel.
To enter this mode, hold the Enter, Up and Down buttons together for approximately 3 seconds until the message CLrA appears on the
display. CLrA is the first option in the menu consisting of the following options:
Display
Option
CLrA
Clear the address/name from the controller
ESC
Exit Setup mode
Pressing the Enter button to select the CLrA option will cause the ‘CLrA’ message to flash for confirmation, if the network type is set to
Genus compatible. Press the Enter button to execute the command, Up or Down buttons to cancel. If the network type is not set to
Genus compatible then the ClrA message will not flash and the ESC option can be used to exit the menu.