Mercury 2 & Intuitive Mercury Mini-Pack Installation Guide
www.resourcedm.com
Parameter Descriptions
Number
Parameter
Description
P-01
Transducer Span
Range of the transducer
P-02
Transducer Offset
Transducer value below zero
P-03
Target
Pressure target, control will try to maintain this pressure
P-04
Target Above P-03
Set-point above the target, used to obtain a “dead-band”
P-05
Target Below P-03
Set-point above the target, used to obtain a “dead-band”
P-06
Stages
Number of stages in the system
P-07
Stage On Delay
Delay time between stages on
P-08
Stage Off Delay
Delay time between stages off
P-09
Fail Off / On
The following will occur in the event of pressure transducer fault.
If set to On then all Compressors or Fans will turn On in the event of a transducer failure. If set to Off then
all Compressors or Fans will turn Off in the event of a transducer failure.
P-10
Service Time
Time controller is running (in 1000 x hours) before the service icon (Spanner icon) comes on. Reset the
spanner icon to off by changing this parameter to 0 and then back to the desired service interval.
P-11
Run Proof
See section : Run Proof
P-12
Optimisation Limit
This is an offset that is added to the target pressure when using the Data Manager Energy feature Pack
Optimisation. For example if target pressure is 2.1 Bar and Optimise Limit set to 0.5 Bar. The remote
optimise command will only be able to optimise the current suction setpoint up to a maximum of 2.6 Bar
P-15
Control Type
Selects between Fixed or Floating. For Condenser control only.
Fixed uses the set-point parameter as its target (P-03)
Floating uses the temperature of a selected probe converted to a pressure as the set-point
P-16
Probe Select
Selects the probe that measures the “floating” temperature
(Note : This would be fitted to the Air On of the Condenser)
See note : Floating Head Pressure
P-17
Low Limit
Stops the floating pressure target from going below this level
P-18
High Limit
Stops the floating pressure target from going above this level
P-19
Condenser Offset
Allows for an offset to be added to the ambient temperature probe used in the “floating” set-point feature.
P-20
Alarm Delay
Delay before HP and LP alarms are signalled
P-21
HP Alarm
HP alarm set-point
P-22
LP Alarm
LP alarm set-point, stage off when reached
P-23
LP Shutdown
Point at which LP Shutdown alarm is generated. Note as soon as the LP Shutdown setpoint is reached
any Compressor/Condenser stages, for the associated section, still operating will go off immediately and
does not wait for the LP Shutdown alarm to be created.
P-30
P-34
Status Fault 1
Status Fault 5
Used to select the type of input required
P-40
Status Fault Delay
Time delay before status faults are activated
P-41
General Fault Delay
Time delay before general faults are activated
P-44
Press 0
o
C / 32
o
F
Used to program the temperature to pressure conversion for floating pressure use.
P-45
Press 10
o
C / 50
o
F
Used to program the temperature to pressure conversion for floating pressure use.
P-46
Press 20
o
C / 68
o
F
Used to program the temperature to pressure conversion for floating pressure use.
P-47
Press 30
o
C / 86
o
F
Used to program the temperature to pressure conversion for floating pressure use.
P-48
Press 40
o
C / 104
o
F
Used to program the temperature to pressure conversion for floating pressure use.
P-49
Press 50
o
C / 122
o
F
Used to program the temperature to pressure conversion for floating pressure use.
P-50
P-74
Stage 1 Relay 1
Stage 5 Relay 5
Select the output for this stage
dFLt
Restore default values
Restores factory set points