Mercury Plant Controller Installation Guide
Universal IO
Setting up from controller display, navigate to the screen “Uni” and select from the following table for U-01 to U-08.
This selects what the Universal IO (U-01 to U-08) can be set for.
NOTE: UniIO U-01 to U-03 can only be set as Inputs, UniIO U-04 and U-05 can only be set for Outputs and UniIO
U-06 to U-08 are seen in settings but are not present on the controller hardware and are for future development.
U-01 to U-03 (Variable Inputs) can be set to 0, 1 or 2.
U-04 and U-05 (Variable Outputs) can be set to 3, 4, 5 or 6.
U-06 to U-08 do not use.
0. 4-20mA Input
1. 0-10V Input
2. 0-5V Input
3. 4-20mA Output
4. 0-20mA Output
5. 0-10V Output
6. 0-5V Output
Input Type
The 3 analogue inputs can be set individually to either of the following,
0. 4 20mA Input (Default)
1. 0 10Vdc Input
2. 0 5Vdc Input
Output Type
The 2 analogue outputs can individually be set to either of the following: -
3. 4 20mA Output (Default)
4. 0 20mA Output
5. 0 10V dc Output
6. 0 5Vdc Output
Status Input Type
Navigate to the screen “StA”
Selects whether the status inputs require a 0V return or 24Vac return signal See: Note 1
Select 1 for Input type 0V return
Select 2 for Input type 24V ac return