Mercury Plant Controller Installation Guide
Input/Output table for Pack/Condenser Controller (Type 3)
Number
IO
Range
Units
I-01
Pressure Input 1
-3.4 - 180
Bar
I-02
Pressure Input 2
-3.4 - 180
Bar
I-03
Pressure Input 3
-3.4 - 180
Bar
I-10
I-17
Analogue Input 1
Analogue Input 8
-60 to +128
O
C
I-21
Sect 2 rem Float
-60 to +128
O
C
I-23
Sect 2 Rem drop Leg
-60 to +128
O
C
I-30
I-41
Digital Input 1
Digital Input 12
0 = OK
1 = Alarm
2 = Unused
I-50
Section 1 Run
0 = Off, 1 = On
2 = Unused
I-53
Sect 2 Heat
0 = Off, 1 = On
2 = Unused
I-54
Liquid Level
0 100
%
I-56
Rem Ext 2
-60 to +128
O
C
O-01
O-12
Relay 1
Relay 12
0 = Off, 1 = On
O-31
Variable Output 1
0 100
%
O-32
Variable Output 2
0 100
%
O-41
Optimisation Level Pack 1
-3.4 - 180
Bar
O-52
Section 2 Float Pressure
-3.4 - 180
Bar
O-54
Sect 2 Drop LegTemp
-60 to +128
O
C
O-56
Sect 2 Drop Leg Press
-3.4 - 180
Bar
O-58
Sect 2 Split
0 = Off, 1 = On
O-60
Sect 2 Heat Reclaim
0 = Off, 1 = On
O-62
Section 2 Night Set-back
0 = Off
1 = On
O-64
Section 2 Day Set-back
0 = Off
1 = On
O-70
Sect 1 Bypass
0 = Off, 1 = On
O-71
Sect 2 Bypass
0 = Off, 1 = On
O-72
Section 1 Gas Dump
0 = Off, 1 = On
S-01
Section 1 Control States
(0) Stabilise
(1) Initial
(2) Normal
(3) High Pressure
(4) Low Pressure
(5) Low Shut-down
(6) Transducer Fail
(7) Stand-by