Installation guide

Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
Revision 2.7 Page 62 of 83
Mercury Plant Controller Installation Guide
Input/Output table for Dual Pack Controller (Type 2)
Number
IO
Range
Units
I-01
Pressure Input 1
-3.4 - 180
Bar
I-02
Pressure Input 2
-3.4 - 180
Bar
I-03
Pressure Input 3
-3.4 - 180
Bar
I-10
I-17
Analogue Input 1
Analogue Input 8
-60 to +128
O
C
I-30
I-41
Digital Input 1
Digital Input 12
0 = OK
1 = Alarm
2 = Unused
I-50
Section 1 Run
0 = Off, 1 = On
2 = Unused
I-51
Section 2 Run
0 = Off, 1 = On
2 = Unused
I-54
Liquid Level
0 100
%
O-01
O-12
Relay 1
Relay 12
0 = Off, 1 = On
O-31
Variable Output 1
0 100
%
O-32
Variable Output 2
0 100
%
O-41
Optimisation Level Pack 1
-3.4 - 180
Bar
O-42
Optimisation Level Pack 2
-3.4 - 180
Bar
O-70
Sect 1 Bypass
0 = Off, 1 = On
O-71
Sect 2 Bypass
0 = Off, 1 = On
O-72
Section 1 Gas Dump
0 = Off, 1 = On
O-73
Section 2 Gas Dump
0 = Off, 1 = On
S-01
Section 1 Control States
(0) Stabilise
(1) Initial
(2) Normal
(3) High Pressure
(4) Low Pressure
(5) Low Shut-down
(6) Transducer Fail
(7) Stand-by
S-02
Section 1 Control States
(0) Stabilise
(1) Initial
(2) Normal
(3) High Pressure
(4) Low Pressure
(5) Low Shut-down
(6) Transducer Fail
(7) Stand-by