Mercury Plant Controller Installation Guide
External Target
Pack Controller
To use Sect 1/2 Ext Target (P473/474) instead of Section 1/2 Target Pressure (P-20/40) a status Input must be set
to “Run 1/2 N/O or N/C”.
When the input is activated the Target Pressure will change from (P-20/40) to (P473/474)
When the input is de-activated the Target Pressure will revert back to (P-20/40)
Condenser Controller
Heat Reclaim must be set to “On” or “On/Rly”.
To use Sect 1/2 Ext Target (P473/474) instead of Section 1/2 Target Pressure (P-20/40) a Status Input must be set
to “Run 1/2 N/O or N/C”.
With Heat Reclaim parameter (P440/441) set to “On” the following will occur: -
When the input is activated the Target Pressure will change from (P-20/40) to (P473/474)
When the input is de-activated the Target Pressure will revert back to (P-20/40)
Or
With Heat Reclaim parameter (P440/441) set to “On/Rly” the following will occur: -
When input is activated the Target Pressure will change from (P-20/40) to (P473/474) and turn on the Heat
Reclaim relay output.
When input is de-activated the Target Pressure will revert back to (P-20/40) and turn off the Heat Reclaim
relay output.
Remote TDB Command
To use a Remote Ext Target Set Point sent from a Data Manager TDB Program Instead of the value entered for the
Ext Target setpoint (P473/474), for a Pack or Condenser, then the following must be configured: -
Status Input must be set to “Run 1/2 N/O or N/C” and if required the above for Heat Reclaim has to be set
(P440/441) to either “On” or “On/Rly”.
When input is activated the Target Pressure will change from (P-20/40) to whatever Target Pressure is
being sent from TDB program. The settable range for “Rem Ext 1/2” is -3.4 Bar to 150 Bar.
When input is de-activated the Target Pressure will revert back to (P-20/40)
Send Ext Target Set Point Command to “Rem Ext 1”/ “Rem Ext 2” using a Data Manager TDB program. Analogue
Output block.