Mercury Plant Controller Installation Guide
Configuration of inputs and outputs:
Status Inputs
Section Inputs can be set up as: -
0
Unused
Input is not used
1
Compressor Normally Open
When selectedMake” to generate Compressor Fault
2
Compressor Normally Closed
When selectedBreak” to generate Compressor Fault
3
Condenser Normally Open
When selectedMake” to generate Condenser Fault
4
Condenser Normally Closed
When selected Break” to generate Condenser Fault
5
General Normally Open
When selected “Make” to generate General Fault
6
General Normally Closed
When selectedBreak” to generate General Fault
7
Standby 1 Normally Open
When selectedMake” to place Section 1 into standby and generate Standby
alarm.
8
Standby 1 Normally Closed
When selectedBreak” to place Section 1 into standby and generate
Standby alarm.
9
Standby 2 Normally Open
When selectedMake” to place Section 2 into standby and generate Standby
alarm.
10
Standby 2 Normally Closed
When selectedBreak” to place Section 2 into standby and generate
Standby alarm.
11
Run 1 Normally Open
When selectedBreak to use Sect 1 Ext Target (P473) OR “Rem Ext 1”
See note : Ext Target
12
Run 1 Normally Closed
When selectedMake” input to use Sect 1 Ext Target (P473) OR “Rem Ext 1”
See note : Ext Target
13
Run 2 Normally Open
When selectedBreak” input to use Sect 2 Ext Target (P474) OR “Rem Ext
2” See Note : Ext Target
14
Run 2 Normally Closed
When selectedMake” input to use Sect 2 Ext Target (P474) OR “Rem Ext 2”
See note : Ext Target
15
INV N/O
When selected Break” to signal Inverter Run. See Note : INV Bypass
16
INV N/C
When selectedMake” to signal Inverter Run. See Note : INV Bypass
For the above any alarms will be generated after the Status Fault Delay (P-60) has timed out. Note Standby Alarm
follows the General Fault Delay (P-60)