Mercury Plant Controller Installation Guide
4 = Probe 5
5 = Probe 6
6 = Probe 7
7 = Probe 8
8 = Remote
P411
Section 1 Drop select
0 = Probe 1
1 = Probe 2
2 = Probe 3
3 = Probe 4
4 = Probe 5
5 = Probe 6
6 = Probe 7
7 = Probe 8
8 = Remote
2
P414
Section 1 Pressure at 0
O
C/32
O
F
-3.4 - 180
0.1
Bar
6.0
P415
Section 1 Pressure at 10
O
C/50
O
F
-3.4 - 180
0.1
Bar
8.2
P416
Section 1 Pressure at 20
O
C/68
O
F
-3.4 - 180
0.1
Bar
10.9
P417
Section 1 Pressure at 30
O
C/86
O
F
-3.4 - 180
0.1
Bar
14.2
P418
Section 1 Pressure at 40
O
C/104
O
F
-3.4 - 180
0.1
Bar
18.1
P419
Section 1 Pressure at 50
O
C/122
O
F
-3.4 - 180
0.1
Bar
23.0
P420
Section 1 Low Limit
-3.4 - 180
0.1
Bar
8.2
P421
Section 1 High Limit
-3.4 - 180
0.1
Bar
23.0
P422
Section 1 Condenser offset
0 - 20
0.1
O
C
6
P438
Section 1 Split
0 = Off
1 = On
1
-
0
P430
Section 1 Split Temp
-60.0 128.0
0.1
o
C
7.2
P432
Section 1 Split Temp Diff
0.0 10.0
0.1
o
C
2.0
P434
Sect 1 Split Press
-3.4 - 180
0.1
Bar
15.2
P436
Sect 1 Split Press Diff
-3.4 - 180
0.1
Bar
1.4
P440
Sect 1 Heat reclaim
0 = Off
1 = On
2 = On Rly
1
-
0
P473
Section 1 Ext trgt
-3.4 - 180
0.1
Bar
14.7
P-40
Section 2 Target Pressure
-3.4 - 180
0.1
Bar
12.7
P-41
Section 2 Target Pressure Above P-20
-3.4 - 180
0.1
Bar
0.5
P-42
Section 2 Target Pressure Below P-20
-3.4 - 180
0.1
Bar
0.5
P-43
Section 2 Number of Stages
0 -12
1
-
0
P-44
Section 2 Stage-on Delay
00:00 60:00
00:01
mins/sec
00:10
P-45
Section 2 Stage-off Delay
00:00 99:00
00:01
mins/sec
00:10
P-46
Section 2 Inverter
0 = Off
1 = On
1
-
0
P443
Section 2 INV Bypass
0 = Disabled
1 = 1 + no retries
2 = 1 + 1 retry
3 = 1 + 2 retries
4 = 1 + 3 retries
5 = 1 + 4 retries
1
-
0
P445
Section 2 INV Minimum
0 - 100
1
%
0
P447
Section 2 INV Maximum
0 - 100
1
%
100
P-47
Section 2 Response On Speed
1 - 60
1
-
5
P-48
Section 2 Response Off Speed
1 - 60
1
-
5
P-50
Section 2 Alarm Delay
00:00 99:00
01:00
mins/sec
05:00
P-51
Section 2 HP Alarm
-3.4 - 180
0.1
Bar
17.9
P-52
Section 2 LP Alarm
-3.4 - 180
0.1
Bar
6.8