Mercury Plant Controller Installation Guide
P435
Sect 2 Split Press
-3.4 - 180
0.1
Bar
15.2
P437
Sect 2 Split Press Diff
-3.4 - 180
0.1
Bar
1.4
P441
Sect 2 Heat reclaim
0 = Off
1 = On
2 = On Rly
1
-
0
P474
Sect 2 Ext Trgt
-3.4 - 180
0.1
O
C
14.7
P475
Dis Trip
-3.4 - 180
0.1
Bar
22.8
P476
Dis Diff
-3.4 - 180
0.1
Bar
2.0
P472
Run Proof
0 = Off, 1 = On
1
0
P-60
Status fault Delay
00:00 60:00
00:01
mins/sec
00:10
P-61
General Alarm Delay
00:00 60:00
00:01
mins/sec
00:10
P480
Liquid Level
0 = Off, 1 = On
1
-
0
P481
High Liquid Level
0 - 100
1
%
80
P482
Low Liquid Level
0 - 100
1
%
20
P483
Liquid Level Alarm Delay
00:00 99:00
01:00
mins:sec
05:00
P494
Dual Standby See Standby Mode
0 = Off, 1 = On
1
-
1
P-80
P-91
Status Fault 1
Status Fault 12
(0) Unused
(1) Comp N/O
(2) Comp N/C
(3) Cond N/O
(4) Cond N/C
(5) Gen N/O
(6) Gen N/C
(7) Standby 1 N/O
(8) Standby 1 N/C
(9) Standby 2 N/O
(10) Standby 2 N/C
(11) Run 1 N/O
(12) Run 1 N/C
(13) Run 2 N/O
(14) Run 2 N/C
(15) INV N/O
(16) INV N/C
1
-
0
P100
P111
Section 1 Stage 1 Relay 1
Section 1 Stage 1 Relay 12
0 = off
1 = on
1
-
0
P112
P123
Section 1 Stage 2 Relay 1
Section 1 Stage 2 Relay 12
0 = off
1 = on
1
-
0
P124
P135
Section 1 Stage 3 Relay 1
Section 1 Stage 3 Relay 12
0 = off
1 = on
1
-
0
P136
P147
Section 1 Stage 4 Relay 1
Section 1 Stage 4 Relay 12
0 = off
1 = on
1
-
0
P124
P135
Section 1 Stage 3 Relay 1
Section 1 Stage 3 Relay 12
0 = off
1 = on
1
-
0