Mercury Plant Controller Installation Guide
P447
Section 2 INV Maximum
0 - 100
1
%
100
P-47
Section 2 Response On Speed
1 - 60
1
-
5
P-48
Section 2 Response Off Speed
1 - 60
1
-
5
P-50
Section 2 Alarm Delay
00:00 99:00
01:00
mins/sec
05:00
P-51
Section 2 HP Alarm
-3.4 - 180
0.1
Bar
17.9
P-52
Section 2 LP Alarm
-3.4 - 180
0.1
Bar
6.8
P-53
Section 2 LP Shut-down
-3.4 - 180
0.1
Bar
6.2
P-35
Section 2 Low Alarm
00:00 99:00
01:00
mins/sec
00:00
P449
Section 2 Fail
0 = Off, 1 = On
1
-
0
P450
Section 2 Sticky Fans
0 - 12
1
-
0
P451
Section 2 Night Set Back
0 = Off
1 = On
2 = Local
3 = Remote
1
-
0
P452
Section 2 Night Reduction
0 - 100
1
%
30
P453
Section 2 Night Set Back On Time
00:00 23:59
00:01
mins/sec
20:00
P454
Section 2 Night Set Back Off Time
00:00 23:59
00:01
mins/sec
08:00
P455
Section 2 Night Set Back Pressure Limit
-3.4 - 180
0.1
Bar
25
P456
Section 2 Day Reduction
0 - 100
1
%
25
P457
Section 2 Day Pressure Limit
-3.4 - 180
0.1
Bar
25
P458
Section 2 Transducer fail Level
0 - 100
1
%
45
P459
Section 2 Control Type
0 = Fixed
1 = Floating
2 = Float Drop
1
-
0
P460
Section 2 Float Select
0 = Probe 1
1 = Probe 2
2 = Probe 3
3 = Probe 4
4 = Probe 5
5 = Probe 6
6 = Probe 7
7 = Probe 8
8 = Remote
1
-
0
P412
Section 2 Drop Select
0 = Probe 1
1 = Probe 2
2 = Probe 3
3 = Probe 4
4 = Probe 5
5 = Probe 6
6 = Probe 7
7 = Probe 8
8 = Remote
P461
Section 2 Pressure at 0
O
C/32
O
F
-3.4 - 180
0.1
Bar
6.0
P462
Section 2 Pressure at 10
O
C/50
O
F
-3.4 - 180
0.1
Bar
8.2
P463
Section 2 Pressure at 20
O
C/68
O
F
-3.4 - 180
0.1
Bar
10.9
P464
Section 2 Pressure at 30
O
C/86
O
F
-3.4 - 180
0.1
Bar
14.2
P465
Section 2 Pressure at 40
O
C/104
O
F
-3.4 - 180
0.1
Bar
18.1
P466
Section 2 Pressure at 50
O
C/122
O
F
-3.4 - 180
0.1
Bar
23.0
P467
Section 2 Low Limit
-3.4 - 180
0.1
Bar
8.2
P468
Section 2 High Limit
-3.4 - 180
0.1
Bar
23.0
P469
Section 2 Condenser offset
0 - 20
0.1
O
C
6
P439
Section 2 Split
0 = Off, 1 = On
1
-
0
P431
Section 2 Split Temp
-60 - 128
0.1
O
C
7.2
P433
Section 2 Split Temp Diff
0.0 10.0
0.1
O
C
2.0