Installation guide

Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
Revision 2.7 Page 33 of 83
Mercury Plant Controller Installation Guide
P445
Section 2 INV Minimum
0 - 100
1
%
0
P447
Section 2 INV Maximum
0 - 100
1
%
100
P491
Section 2 Gas Dump
0 = Off, 1 = On
1
-
0
P493
Section 2 Gas diff
-3.4 - 180
0.1
Bar
0.5
P471
Section 2 Always Run last
0 = Off, 1 = On
1
-
0
P-47
Section 2 Response On Speed
1 - 60
1
-
5
P-48
Section 2 Response Off Speed
1 - 60
1
-
5
P-49
Section 2 Optimise Limit
-3.4 - 180
0.1
Bar
2.0
P-50
Section 2 Alarm Delay
00:00 99:00
01:00
mins/sec
05:00
P-51
Section 2 HP Alarm
-3.4 - 180
0.1
Bar
4.1
P-52
Section 2 LP Alarm
-3.4 - 180
0.1
Bar
0.6
P-53
Section 2 LP Shut-down
-3.4 - 180
0.1
Bar
0.4
P-35
Section 2 Low Alarm
00:00 99:00
01:00
mins/sec
00:00
P449
Section 2 Fail
0 = Off, 1 = On
1
-
0
P472
Run Proof
0 = Off, 1 = On
1
0
P-60
Status fault Delay
00:00 60:00
00:01
mins/sec
00:10
P-61
General Alarm Delay
00:00 60:00
00:01
mins/sec
00:10
P480
Liquid Level
0 = Off, 1 = On
1
-
0
P481
High Liquid Level
0 - 100
1
%
80
P482
Low Liquid Level
0 - 100
1
%
20
P483
Liquid Level Alarm Delay
00:00 99:00
01:00
mins:sec
05:00
P494
Dual Standby See Standby Mode
0 = Off, 1 = On
1
-
1
P-80
P-91
Status Fault 1
Status Fault 12
(0) Unused
(1) Comp N/O
(2) Comp N/C
(3) Cond N/O
(4) Cond N/C
(5) Gen N/O
(6) Gen N/C
(7) Standby 1 N/O
(8) Standby 1 N/C
(9) Standby 2 N/O
(10) Standby 2 N/C
(11) Run 1 N/O
(12) Run 1 N/C
(13) Run 2 N/O
(14) Run 2 N/C
(15) INV N/O
(16) INV N/C
1
-
0
P100
P111
Section 1 Stage 1 Relay 1
Section 1 Stage 1 Relay 12
0 = off
1 = on
1
-
0
P112
P123
Section 1 Stage 2 Relay 1
Section 1 Stage 2 Relay 12
0 = off
1 = on
1
-
0
P124
P135
Section 1 Stage 3 Relay 1
Section 1 Stage 3 Relay 12
0 = off
1 = on
1
-
0