Mercury Plant Controller Installation Guide
P196
P207
Section 1 Stage 9 Relay 1
Section 1 Stage 9 Relay 12
0 = off
1 = on
1
-
0
P208
P219
Section 1 Stage 10 Relay 1
Section 1 Stage 10 Relay 12
0 = off
1 = on
1
-
0
P220
P231
Section 1 Stage 11 Relay 1
Section 1 Stage 11 Relay 12
0 = off
1 = on
1
-
0
P232
P243
Section 1 Stage 12 Relay 1
Section 1 Stage 12 Relay 12
0 = off
1 = on
1
-
0
dFLt
Restore Default Settings
(Front panel Only)
ESc
* Span and Offset allows for the full range of the transducer to be used by the controller.
Span is the full range of the transducer
Offset is the value below zero.
Note. The controller uses absolute pressure; if guage pressure is required, add +1 Bar to the offset value.
Example: Danfoss AKS 33 with range: -1 bar to 12 bar
Span would be 190 (13 bar)
Offset would be -15 (-1 bar)
If only transducer input 1 in use please see Note 10 also.