Mercury Plant Controller Installation Guide
Parameter table for Pack Controller (Type 6, Staged)
Number
Parameter
Range
Step
Units
Default
P-01
Transducer 1 Span *
-3.4 - 180
0.1
Bar
13.8
P-02
Transducer 1 Offset
-3.4 - 180
0.1
Bar
0
P-03
Transducer 2 Span *
-3.4 - 180
0.1
Bar
13.8
P-04
Transducer 2 Offset
-3.4 - 180
0.1
Bar
0
P-05
Transducer 3 Span *
-3.4 - 180
0.1
Bar
13.8
P-06
Transducer 3 Offset
-3.4 - 180
0.1
Bar
0
P-20
Section 1 Target Pressure
-3.4 - 180
0.1
Bar
2.1
P473
Section 1 External Target Pressure
-3.4 - 180
0.1
Bar
3.1
P-21
Section 1 Target Pressure Above P-20
-3.4 - 180
0.1
Bar
0.5
P-22
Section 1 Target Pressure Below P-20
-3.4 - 180
0.1
Bar
0.5
P-23
Section 1 Number of Stages
0 -12
1
-
0
P-24
Section 1 Stage-on Delay
00:00 – 60:00
00:01
mins/sec
00:10
P-25
Section 1 Stage-off Delay
00:00 – 99:00
00:01
mins/sec
00:10
P-26
Section 1 Inverter
0 = Off
1 = On
1
-
0
P442
Section 1 INV Bypass
0 = Disabled
1 = 1 + no retries
2 = 1 + 1 retry
3 = 1 + 2 retries
4 = 1 + 3 retries
5 = 1 + 4 retries
1
-
0
P444
Section 1 INV Minimum
0 - 100
1
%
0
P446
Section 1 INV Maximum
0 - 100
1
%
100
P490
Section 1 Gas Dump
0 = Off
1 = On
1
-
0
P492
Section 1 Gas Diff
-3.4 - 180
0.1
Bar
0.5
P470
Section 1 Always Run last
0 = Off
1 = On
1
-
0
P-27
Section 1 Response On Speed
1 - 60
1
-
5
P-28
Section 1 Response Off Speed
1 - 60
1
-
5
P-29
Section 1 Optimise Limit
-3.4 - 180
0.1
Bar
2.0
P-30
Section 1 Alarm Delay
00:00 – 99:00
01:00
mins/sec
05:00
P-31
Section 1 HP Alarm
-3.4 - 180
0.1
Bar
4.1
P-32
Section 1 LP Alarm
-3.4 - 180
0.1
Bar
0.6
P-33
Section 1 LP Shut-down
-3.4 - 180
0.1
Bar
0.4
P-34
Section 1 Low Alarm
00:00 – 99:00
01:00
mins/sec
00:00
P448
Section 1 Fail
0 = Off, 1 = On
1
-
0
P472
Run Proof
0 = Off, 1 = On
1
0
P-60
Status fault Delay
00:00 – 60:00
00:01
mins/sec
00:10
P-61
General Alarm Delay
00:00 – 60:00
00:01
mins/sec
00:10
P480
Liquid Level
0 = Off
1 = On
1
-
0
P481
High Liquid Level
0 - 100
1
%
80
P482
Low Liquid Level
0 - 100
1
%
20
P483
Liquid Level Alarm Delay
00:00 – 99:00
01:00
mins:sec
05:00