Mercury Plant Controller Installation Guide
Parameter table for Condenser Controller (Type 5, Fuzzy)
Number
Parameter
Range
Step
Units
Default
P-01
Transducer 1 Span *
-3.4 - 180
0.1
Bar
34.4
P-02
Transducer 1 Offset
-3.4 - 180
0.1
Bar
0
P-03
Transducer 2 Span *
-3.4 - 180
0.1
Bar
13.8
P-04
Transducer 2 Offset
-3.4 - 180
0.1
Bar
0
P-05
Transducer 3 Span *
-3.4 - 180
0.1
Bar
13.8
P-06
Transducer 3 Offset
-3.4 - 180
0.1
Bar
0
P-20
Section 1 Target Pressure
-3.4 - 180
0.1
Bar
12.7
P-21
Section 1 Target Pressure
Above P-20
-3.4 - 180
0.1
Bar
0.5
P-22
Section 1 Target Pressure
Below P-20
-3.4 - 180
0.1
Bar
0.5
P-26
Section 1 Inverter
0 = Off, 1 = On
1
-
0
P442
Section 1 INV Bypass
0 = Disabled
1 = 1 + no retries
2 = 1 + 1 retry
3 = 1 + 2 retries
4 = 1 + 3 retries
5 = 1 + 4 retries
1
-
0
P444
Section 1 INV Minimum
0 - 100
1
%
0
P446
Section 1 INV Maximum
0 - 100
1
%
100
P-27
Section 1 Response On Speed
1 - 60
1
-
5
P-28
Section 1 Response Off Speed
1 - 60
1
-
5
P-30
Section 1 Alarm Delay
00:00 – 99:00
01:00
mins/sec
05:00
P-31
Section 1 HP Alarm
-3.4 - 180
0.1
Bar
17.9
P-32
Section 1 LP Alarm
-3.4 - 180
0.1
Bar
6.8
P-33
Section 1 LP Shut-down
-3.4 - 180
0.1
Bar
6.2
P-34
Section 1 Low Alarm
00:00 – 99:00
01:00
mins/sec
00:00
P448
Section 1 Fail
0 = Off, 1 = On
1
-
0
P400
Section 1 Sticky Fans
0 - 12
1
-
0
P401
Section 1 Night Set Back
0 = Off, 1 = On
2 = Local
3 = Remote
1
-
0
P402
Section 1 Night Reduction
0 - 100
1
%
30
P403
Section 1 Night Set Back On
Time
00:00 – 23:59
00:01
mins/sec
20:00
P404
Section 1 Night Set Back Off
Time
00:00 – 23:59
00:01
mins/sec
08:00
P405
Section 1 Night Set Back
Pressure Limit
-3.4 - 180
0.1
Bar
25
P406
Section 1 Day Reduction
0 - 100
1
%
25
P407
Section 1 Day Pressure Limit
-3.4 - 180
0.1
Bar
25
P408
Section 1 Transducer fail Level
0 - 100
1
%
45
P409
Section 1 Control Type
0 = Fixed
1 = Floating
2 = Float Drop
1
-
0
P410
Section 1 Float Select
0 = Probe 1
1 = Probe 2
2 = Probe 3
3 = Probe 4
4 = Probe 5
5 = Probe 6
6 = Probe 7
7 = Probe 8
8 = Remote
1
-
1