Mercury Plant Controller Installation Guide
P-61
General Alarm Delay
00:00 60:00
00:01
mins/sec
00:10
P480
Liquid Level
0 = Off, 1 = On
1
-
0
P481
High Liquid Level
0 - 100
1
%
80
P482
Low Liquid Level
0 - 100
1
%
20
P483
Liquid Level Alarm Delay
00:00 99:00
01:00
mins:sec
05:00
P-80
P-91
Status Fault 1
Status Fault 12
(0) Unused
(1) Comp N/O
(2) Comp N/C
(3) Cond N/O
(4) Cond N/C
(5) Gen N/O
(6) Gen N/C
(7) Standby 1 N/O
(8) Standby 1 N/C
(9) Standby 2 N/O
(10) Standby 2 N/C
(11) Run 1 N/O
(12) Run 1 N/C
(13) Run 2 N/O
(14) Run 2 N/C
(15) INV N/O
(16) INV N/C
1
-
0
P100
P111
Section 1 Stage 1
Section 1 Stage 12
(0) None,
(1) Unused,
(2) Compressor,
(3) Loader,
(4) Fan
(5) Inverter
(6) Trim
(7) Comp Run
1
-
0
P120
P131
Section 1 Stage 1 Size
Section 1 Stage 12 Size
0.0 60.0
0.1
-
0.0
dFLt
Restore Default Settings
(Front panel Only)
ESc
* Span and Offset allows for the full range of the transducer to be used by the controller.
Span is the full range of the transducer
Offset is the value below zero.
Note. The controller uses absolute pressure; if gauge pressure is required, add +1 Bar to the offset value.
Example: Danfoss AKS 33 with range: -1 bar to 12 bar
Span would be 190 (13 bar)
Offset would be -15 (-1 bar)
If only transducer input 1 is in use please see Note 10 also.
**Run smallest=on: - When all compressors are off (because the target pressure has been satisfied) the controller,
when the pressure rises, will always turn on the smallest compressor after the variable output has reached 100%. If
the ASC timer is running for the smallest compressor, the controller will NOT bring on any other available
compressors, the variable output will remain at 100% and the controller will wait until the ASC timer has elapsed
and then turn on the smallest.
Please note that this is true for any pressure condition.