Installation guide
Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
Revision 2.7 Page 11 of 83
Mercury Plant Controller Installation Guide
Note: If the units are set to
O
C, pressure will be displayed in Bar, if units are set to
O
F, pressure will be displayed in
PSI.
Unit
Number
Probe Type
Units
0
Probes not used
O
C
1
PT1000
O
C
2
PT1000
O
F
3
NTC2K
O
C
4
NTC2K
O
F
5
NTC470R
O
C
6
NTC470R
O
F
7
NTC700R
O
C
8
NTC700R
O
F
9
NTC3K
O
C
10
NTC3K
O
F
11
NTC2K25
O
C
12
NTC2K25
O
F
13
NTC100K
O
C
14
NTC100K
O
F
15
NTC5K
O
C
16
NTC5K
O
F
17
NTC6K
O
C
18
NTC6K
O
F
19
NTC10K
O
C
20
NTC10K
O
F
21
NTC10K (2)
O
C
22
NTC10K (2)
O
F
Temperature probe range -60 degree Celsius to +128 degree Celsius.
Set/View Offset
This feature allows the probe display temperature to be offset by the value selected: Each of the 8 probes has an
individual offset, see the table below: - C-01 = Probe 1 etc.
Note: This can only be set at the controller display and cannot be set remotely by a Data Manager front-end.
OFSt Display
Range
Step
Default
C-01
±20
O
0.1
0
C-02
±20
O
0.1
0
C-03
±20
O
0.1
0
C-04
±20
O
0.1
0
C-05
±20
O
0.1
0
C-06
±20
O
0.1
0
C-07
±20
O
0.1
0
C-08
±20
O
0.1
0