ML Twin Controller Installation Guide
www.resourcedm.com
Parameter Tables
No.
Parameter
Range
O
C (
O
F)
Step
Units
Default
P-15
Lead Cut-In
-60.0 (-76.0) to +60.0 (140.0)
0.1
O
C (
O
F)
3.0 (37.4)
P-16
Lead Diff
-60.0 (-76.0) to +60.0 (140.0)
0.1
O
C (
O
F)
3.0 (5.4)
P-17
Lag Cut-In
-60.0 (-76.0) to +60.0 (140.0)
0.1
O
C (
O
F)
6.0 (42.8)
P-18
Lag Diff
-60.0 (-76.0) to +60.0 (140.0)
0.1
O
C (
O
F)
3.0 (5.4)
P-03
Control Weight
0 to 100
1
%
50
P-04
Probe 3 Type
0 = Off
1 = Monitor
2 = Monitor with Fault
3 = Monitor with Alarm
4 = Defrost term
5 = Plant N/O
6 = Plant N/C
1
-
0
P-05
Probe 4 Type
0 = Off
1 = Monitor
2 = Monitor with Fault
3 = Monitor with Alarm
4 = Defrost term
5 = Plant N/O
6 = Plant N/C
1
-
0
P-06
Relay 2 Function
0 = Fans
1 = Lights
2 = Trims
3 = Alarm
4 = SLV
5 = Trim Hub
6 = Comp
1
-
6
P-07
Relay 4 Function
0 = Fans
1 = Lights
2 = Trims
3 = Alarm
4 = SLV
5 = Trim Hub
1
-
1
P-08
Relay 5 Function
0 = Fans
1 = Lights
2 = Trims
3 = Alarm
4 = SLV
5 = Trim Hub
1
-
2
P-11
Trim level
0 to 100
1
%
100
P-12
Anti Short Cycle Time
00:00 to 99:00
01:00
mins:secs
01:00
P-14
Service Interval
0 to 128
1
KHrs
60
P-20
Alarm delay
00:00 to 99:00
01:00
mins:secs
20:00
P-21
Under Temp Alarm
-60.0 (-76.0) to +60.0 (140.0)
0.1
O
C (
O
F)
-2.0 (28.4)
P-22
Over Temp Alarm
-60.0 (-76.0) to +60.0 (140.0)
0.1
O
C (
O
F)
5.0 (41.0)
P-23
Monitor probe Alarm delay
00:00 to 99:00
01:00
mins:secs
20:00
P-24
Monitor probe Under Temp
-60.0 (-76.0) to +60.0 (140.0)
0.1
O
C (
O
F)
-2.0 (28.4)
P-25
Monitor probe Over Temp
-60.0 (-76.0) to +60.0 (140.0)
0.1
O
C (
O
F)
5.0 (41.0)
P-26
Alarm buzzer duration
00:00 to 61:00
01:00
mins:secs
00:00
P-40
Defrost Mode
0 = Local
1 = Remote
1
-
0
P-41
Defrost Start Time (Local
mode)
00:00 to 23:59
00:01
hrs:min
01:00
P-42
Defrost number (Local
mode)
0 to 8
1
-
6
P-43
No Defrost Time
0 to 180
1
Hrs
12
P-44
Defrost Termination
Temperature
-60.0 (-76.0) to +60.0 (140.0)
0.1
O
C (
O
F)
10.0 (50.0)
P-45
Defrost Time
00:00 to 99:00
01:00
mins:secs
20:00
P-46
Defrost Type
0 = Electric
1 = Gas
2 = Off Cycle
1
-
0
P-47
Drain Down Time
00:00 to 24:00
00:15
mins:secs
02:30
P-48
Recovery Time
00:00 to 99:00
01:00
mins:secs
30:00