Mercury 3 M & E Installation Guide
www.resourcedm.com
The Mercury 3 Range
From Resource Data Management
For Version 1.0M & 1.0E
The Mercury Mk3 controller is primarily intended for use in refrigeration display cabinets or coldroom applications. It will switch the
evaporator valve (LLV or EEV) based on the value of its temperature or pressure input. It has outputs to control lights, fans, suction valve,
trim heaters and defrost control. It can have variable inputs for reading a pressure transducer along with two digital inputs that can be
added to, by utilising the switched resistors feature.
The controller has many features, some of which are energy saving, such as pulsed trim heaters or the case off with lights parameter
(see parameter section for further details). There are several hardware variants of the Mercury Mk3 controller split into two types; an E-
version that has Relay 1 as a Solid State Relay for switching EEVs and the second is an M-version that has Relay 1 as an electro-
mechanical relay for switching solenoid LLVs. For these two types, there are further options of adding analogue inputs, choice of serial
or built in IP communications along with either a remote or integral display option (see ordering information for more details).
The controller supports PT1000, NTC2K, 470R, 700R, 3K, 5K, 6K, NTC2K25, NTC10K or NTC10K(2) temperature probes.
Note: probe types cannot be mixed.
Hardware Variants
As mentioned above, the Mercury 3 controller offers a number of choices concerning the physical hardware including choice of IO,
Display and communications type. Furthermore depending on the valve type (electronic expansion or mechanical solenoid valve) the
option of either a solid state or mechanical relay is available. For specific part numbers see Ordering Information.
Inputs/ Outputs
Relay 1
Display
Comms
6 Probe, 2 Digital Inputs / 5 Relay Outputs
Mechanical Relay
Integral/ Remote
Display
Serial/
Ethernet
6 Probe, 2 Digital & 2 Analogue Inputs / 5 Relay Outputs
Solid State Relay
Compatible Displays
The following displays are compatible with the Mercury Remote Display Controllers:-
Description
Part Number
Mercury Remote Display with 5m cable
PR0325
Mercury Keyswitch Remote Display with 5m cable
PR0326
Mercury DIN Remote Display with 5m cable
PR0327
Mercury DIN Keyswitch Remote Display with 5m cable
PR0328
Mercury mk2 Remote Display with 5m cable
PR0725
Configuration
The controller gives you up to six configuration options (see ‘Type’ menu):-
Display value
Mercury Mk3 Mechanical Expansion Valve
Mercury Mk3 Electronic Expansion Valve
1
Integral controller (HT)
N/A
2
Integral controller (LT)
N/A
3
Remote piped case controller (LT)
Remote piped case controller (LT)
4
Remote piped case controller (HT)
Remote piped case controller (HT)
5
Coldroom controller (LT)
Coldroom controller (LT)
6
Coldroom controller (HT)
Coldroom controller (HT)
Note: The controllers are delivered pre-configured as Type 1 and Type 3 for variants M and E respectively.
Compatible Network Interfaces
Mercury controllers which do not have an IP interface built in are capable of connecting to either a TCP/IP local area network, an RS485
Genus compatible network, an RDM wireless mesh network or they can be used in standalone mode with no network output. To connect
to a network you must add the correct communications module. Connecting to any of these communication modules will automatically be
detected on power up and will affect the Net’ menu set up screens available to you. Note controllers with built in IP will be able to
communicate to any IP switch, including the rear ports of the RDM Mercury Hub.
Description
Part Number
IP Futura (Single Mercury to IP Interface)
PR0016
RS485 Interface (Single Mercury to RS485 Interface)
PR0026
Mercury IP Switch (IP support for 10 controllers)
PR0018
Mercury IP Switch with Pressure/Humidity Inputs
PR0018-PHI
Wireless Mesh Interface (for single Mercury)
PR0730