User guide
Revision 1.0 Page 12 of 29
Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
Mercury 3 M & E Installation Guide
www.resourcedm.com
Drain Down
(Integral)
00:00 to 24:00
00:15
mm:ss
01:30
00:30
P-48
Recovery Time
00:00 to 99:00
01:00
mm:ss
30:00
30:00
P-89
Pump Down Time
00:00 to 99:00
01:00
mm:ss
00:00
00:00
P-86
Fan Delay mode
0 = Time 1 = Temp
1
0
0
P-49
Fan Delay Time
Types (Cabinet)
00:00 to 99:00
01:00
mm:ss
00:00
00:00
Fan Delay Time
Types (Integral &
Coldroom)
00:00 to 99:00
01:00
mm:ss
03:00
03:00
P-88
Fan Delay Temp
-42 to 30 (-43.6 to 86)
0.1
Deg
-20 (-4)
0.0 (32)
P-50
Fans In Defrost
0 (Off), 1 (On)
On
On
Fans In Defrost
(Coldroom)
0 (Off), 1 (On)
Off
Off
P-91
Defrost Type M & E
0 = Elec. 1 = Elce/CIn
1
0
0
Defrost Type
(Integral)
0 = Elec. 1 = Gas.
2 = Elec CIn
P-94
Defrost Hold
0 (Off), 1 (On)
Off
Off
P-95
Defrost Skip
0 (Off), 1 (On)
Off
Off
P-96
Defrost Skip Time
00:00 to 99:00
01:00
mm:ss
12:00
12:00
P-80
Door Alarm Delay
00:00 to 99:00
01:00
mm:ss
20:00
20:00
P-81
Door Closes LL
0 (No), 1 (Yes)
No
No
P-82
Door Stops Fan
0 (No), 1 (Yes)
No
No
P-60
Lights Mode
0 (Local), 1 (Remote),
2 (Man Off), 3(Man On)
Local
Local
P-61
Sun Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-62
Sun Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-63
Mon Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-64
Mon Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-65
Tue Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-66
Tue Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-67
Wed Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-68
Wed Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-69
Thu Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-70
Thu Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-71
Fri Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-72
Fri Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-73
Sat Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-74
Sat Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-30
Broadcast ID
0 to 999
1
0
0
P-31
Refrigerant
See Refrigerant Table
Below
1
0
0
P-32
Pressure Units
0 = Absolute 1 = Gauge
1
0
0
P-33
Evap Offset
0.0 to 1.0
0.1
0.0
0.0
P-34
Glide
0.0 to 5.0
0.1
Deg
0.0
0.0
P-35
Trans Span*
-3.4 to 180.0
0.1
Bar
13.8
13.8
P-36
Trans Offset*
-3.4 to 180.0
0.1
Bar
0.0
0.0
dFLt
Restore defaults
* Transducer Span and Offset allows for the full range of the transducer to be used by the Mercury Controller. ‘Span’ is the full range of
the transducer, ‘Offset’ is the value below zero.
Example: Danfoss AKS 33 with range -1 bar to 12 bar
Span would be 190 (13 bar)
Offset would be -15 (-1 bar)
Refrigerant Table for P-31
No.
Gas
No.
Gas
No.
Gas
No.
Gas
No.
Gas
0
None
6
R32
12
R401A
18
R407A
24
R507
1
R12
7
R114
13
R401B
19
R407B
25
R717
2
R13
8
R134A
14
R402
20
R407C
26
R290
3
R13B1
9
R142B
15
R402A
21
R500
27
R744
4
R22
10
R227
16
R402B
22
R502
28
R407F
5
R23
11
R401
17
R404A
23
R503
29
R410A