User guide

Revision 1.0 Page 11 of 29
Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Mercury 3 M & E Installation Guide
www.resourcedm.com
P-15
Probe 5 Select
0 = Defrost, 1 = Monitor
1
0
0
P-16
Relay 3 Mode
0 = Lights, 1 = Alarm
1
0
0
P-17
Evap Select
0 = Local 1 = Rem1,
2 = Rem2, 3 = Rem3,
4 = Trans V,
5= Trans mA
1
0
0
P-97
Control Fail On/Off
(Mechanical Valve)
00:00 to 10:00
01:00
mm:ss
00:00
00:00
Control Fail Valve
Level (EEV)
0 to 100%
0.1
%
0
0
P-29
Probe 3 Resistor
function
(Mechanical Valve)
0 = Plant fault,
1 = External defrost
1
0
0
Probe 1 Resistor
Function (EEV)
0 = Plant fault,
1 = External defrost
1
0
0
P-18
Service Interval
time
0 to 128
1
KHrs
60
60
P-19
Switch Resistors
0 (Off), 1(On)
1
1
1
P-77
Man Stop LLV/Fans
0 (Off), 1(On)
1
0
0
P-98
Lights Case Off
0 (Off), 1 (On),
2 (Unused)
1
0
0
P-99
Load Shedding
0 (Off), 1 (Mode 1),
2 (Mode 2)
1
0
0
P-100 /
P-101
Digital Input 1 /
Digital Input 2
Types 1&2;
0 (Plant 1), 1 (Switch),
2 (Defrost)
1
DI 1: 0
DI 2: 3
DI 1: 0
DI 2: 3
Types 3&4;
0 (Plant 1), 1 (Switch),
2 (Defrost)
1
DI 1: 0
DI 2: 1
DI 1: 0
DI 2: 1
Types 5&6;
0 (Plant 1), 1 (Switch),
2 (Defrost, 3 (Door),
4 (Man Trap)
1
DI 1: 3
DI 2: 4
DI 1: 3
DI 2: 4
P-20
Alarm Delay
00:00 to 99:00
01:00
mm:ss
20:00
20:00
P-21
Under Temp Alm
-49 to 60 (-56.2 to 140)
0.1
Deg
-30 (-22)
-2 (28.4)
P-22
Over Temp Alm
-49 to 60 (-56.2 to 140)
0.1
Deg
-15 (5)
5 (41)
P-23
Log Probe Type
0 (Off), 1 (Logging),
2 (Logging/Alarm)
Off
Off
P-24
Slug Log Probe
0 (Off), 1 (On)
Off
Off
P-25
Log Alarm Delay
00:00 to 99:00
01:00
mm:ss
20:00
20:00
P-26
Log UT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
-35 (-31)
-1 (30.2)
Log UT Alarm
(Mechanical Valve
Coldroom)
-49 to 60 (-56.2 to 140)
0.1
Deg
-30 (22)
-2 (28.4)
P-27
Log OT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
-12 (10.4)
6 (42.8)
Log OT Alarm
(Mechanical Valve
Coldroom)
-49 to 60 (-56.2 to 140)
0.1
Deg
-15 (5)
5 (41)
P-28
Monitor OT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
20 (68)
20 (68)
P-40
Defrost Mode
0 (Local), 1 (Remote),
2 (External)
Local
Local
P-41
Defrost Start
00:00 to 23:59
00:01
hh:mm
01:00
01:00
P-42
Defrosts per Day
0 to 8
1
6
6
P-43
No Defrost Time
0 to 25
1
hours
8
8
No Defrost Time
(Integral)
0 to 25
1
hours
8
5
No Defrost Time
(EEV)
0 to 25
1
hours
12
12
P-44
Def Terminate
Temp.
-42 to 30 (-43.6 to 86)
0.1
Deg
14 (57.2)
10 (50)
Def Terminate
Temp. (Integral)
-42 to 30 (-43.6 to 86)
0.1
Deg
10 (50)
10 (50)
P-45
Def Min Time
00:00 to 99:00
01:00
mm:ss
05:00
05:00
P-46
Def Max Time
00:00 to 99:00
01:00
mm:ss
24:00
24:00
Def Max Time
(Integral)
00:00 to 99:00
01:00
mm:ss
25:00
30:00
P-47
Drain Down
00:00 to 24:00
00:15
mm:ss
01:30
01:30