User guide
Revision 7.1b Page 30 of 31
Mercury Coldroom Panel Installation Guide
www.resourcedm.com
Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
7) Remove the fixing plate. Swap the MCB in position “F5 Defrost” to “F1 Compressor/LLSV” and the MCB from “F1
Compressor/LLSV” to “F5 Defrost” taking note of the orientation of the MCB.
The image below shows the view of the Coldroom with the fixing plate removed.
8) Ensure the MCB’s are securely fitted and the desired rated MCB’s are in the appropriate positions before re-inserting the fixing
plate.
9) Now secure the fixing plate using the previously removed screws.
10) Reattach the plastic washers to the MCB’s.
11) A secondary label is supplied with the Coldroom panel and must be affixed to indicate that the MCB positions and therefore
ratings have changed for the Compressor/LLV and Defrost MCB.
12) Close the Coldroom panel door and secure the front panel via the two screw fixings.
Warning : Only the Compressor/LLV and Defrost MCB positions are interchangeable. No other MCB positions can be altered.
Instructions – Fuse Variants
1) Before working on this equipment, ensure that the device is fully isolated from any supply voltage, including connections to all relays and other
I/O connectors.
2) Open the Coldroom front panel by unscrewing the screw fixings at the top right and bottom right of the panel door. If an Isolator
switch is fitted to the Coldroom panel then this must be in the off position before the door will open.
3) Locate the Fused outputs.
4) Look at the PCB screen print to identify each output and the associated Fuse. Note the ratings of the Fuse are marked on each
Fuse and they should be checked to ensure the current Fuse rating is correct for the position in which the Fuse is fitted.
5) To swap the higher rated Defrost Fuse over with the Compressor/LLV Fuse firstly remove the rubber cover on each Defrost
and Compressor/LLV Fuse.
6) Now remove and swap the Fuse in position “F5 Defrost” to “F1 Compressor/LLSV” and the Fuse from “F1 Compressor/LLSV”
to “F5 Defrost”.
7) Ensure the Fuses are securely fitted and the desired rated Fuse is in the appropriate position.
8) Now reattached the rubber cover over each Fuse ensuring the fuse and holder is fully covered.
9) Close the Coldroom panel door and secure the front panel via the two screw fixings.
Warning : Only the Compressor/LLV and Defrost Fuse positions are interchangeable. No other Fuse positions can be altered.