Specification
Power requirements
Supply Voltage Range: 100 - 240 Vac ±10%
Supply Frequency: 50 - 60 Hz
Maximum supply current: 40 Amps
Operating temperature range: +5
0
C to +50
0
C
Operating Humidity: 80% maximum
Storage temperature range: -20
0
C to +65
0
C
Environmental: Indoor use at altitudes up to 2000m, Pollution Degree 1,
Voltage fluctuations not to exceed ±10% of nominal voltage
Size: 240mm (W) x 300mm (H) x 140mm (D)
Weight: 2.2 Kilograms
Safety: EN61010
This device MUST be earthed
EMC: EN61326; 1997 +Amdt. A1; 1998
Ventilation: There is no requirement for forced cooling ventilation
The host equipment must provide a suitable external over-current protection device such as: -
Fuse: 40A 240 Vac Antisurge (T) HRC conforming to IEC 60127
Or MCB: 40A, 240 VAC Type C conforming to BS EN 60898
IP Rating IP 40
The host equipment must provide adequate protection against contact to hazardous live parts.
Maximum Output Loads
Note in later Coldroom panel hardware revisions, Revision 2, the Compressor/LLV, Fans and Defrost ratings have been revised. Please
view the appropriate listing, shown below, depending on the hardware revision in use. A visual inspection of the Coldroom panel must
take place to determine the hardware revision. A label is affixed alongside the relay outputs highlighting the current rating in Amps.
Note in Revision 2 the Compressor/LLV and Defrost MCB or Fuse can be interchanged to allow the higher rated MCB or Fuse to be used
on the Compressor/LLV relay output and the lower rated MCB or fuse to be used on the Fans relay output. Please see Appendix 1
Revision 1 (Earlier Hardware)
Compressor/LLV: 15A (non inductive) 8A CosФ=0.4: Motor Load (CosФ=0.6) ½ HP
Switched Output Voltage: Same as supply voltage
EEV: 5A (non inductive) 2A CosФ=0.4
Switched Output Voltage: Same as supply voltage
Defrost: 15A (non inductive) 8A CosФ=0.4
Switched Output Voltage: Same as supply voltage
Fans: 10A (non inductive) 8A CosФ=0.4
Switched Output Voltage: Same as supply voltage
Lights: 6A (non inductive) 6A CosФ=0.4
Switched Output Voltage: Same as supply voltage
Out 1: 5A
Permanent Output Voltage: Same as supply voltage
Out 2: 1A
Permanent Output Voltage: Same as supply voltage
Revision 2
Compressor/LLV: 10A (non inductive) User configuration dependant see Appendix 1
8A CosФ=0.4: Motor Load (CosФ=0.6) ½ HP
Switched Output Voltage: Same as supply voltage
EEV: 5A (non inductive) 2A CosФ=0.4
Switched Output Voltage: Same as supply voltage
Defrost: 20A (non inductive) User configuration dependant see Appendix 1
8A CosФ=0.4
Switched Output Voltage: Same as supply voltage
Fans: 8A (non inductive) 8A CosФ=0.4
Switched Output Voltage: Same as supply voltage