User guide

Revision 7.1b Page 22 of 31
Mercury Coldroom Panel Installation Guide
www.resourcedm.com
Ensure that all power is
switched off before
installing or maintaining
this product
O-30
Set Point Offset
-49 to 60 (-56.2 to 140)
0.1
Deg
O-32
Timer
0 (Off), 1 (On)
O-18
Run Time
0 to 128
1
K Hrs
S-01
Control State
0 (Stabilise), 1 (Normal),
2 (Defrost Min), 3 (Defrost Max),
4 (Drain Down), 5 Fan Delay
6 (Recovery), 7 (OT Alarm),
8 (UT Alarm), 9 (Fans Only),
10 (Lights Only), 11 (Case Off),
12 (Pump_Down), 13 (Df Hold),
14 (Load Shedding)
Input/Output table for Coldroom Panel with EEV option
Number
IO
Range (dependant on probe type)
o
C (
o
F )
Step
Units
I-01
Control Temp.
-42 to 60 (-43.6 to 140)
0.1
Deg
I-02
Display temp
-42 to 60 (-43.6 to 140)
0.1
Deg
I-03
Air on Probe
-42 to 60 (-43.6 to 140)
0.1
Deg
I-04
Air off Probe
-42 to 60 (-43.6 to 140)
0.1
Deg
I-05
Evaporator Probe
-49 to 60 (-56.2 to 140)
0.1
Deg
I-06
Suction Line Probe
-49 to 60 (-56.2 to 140)
0.1
Deg
I-07
Superheat
-30 to 60 (-54 to 108)
0.1
Deg
I-08
Logging Probe
-49 to 60 (-56.2 to 140)
0.1
Deg
I-09
Defrost Probe
-49 to 60 (-56.2 to 140)
0.1
Deg
I-10
Plant fault
0 (OK), 1 (Alarm)
I-11
Case Clean
0 (Off), 1 (On)
I-12
Door Sensor
0 (Off), 1 (On)
I-13
Person trapped
0 (OK), 1 (Alarm)
I-15
Remote Evap In Temp
-49 to 60 (-56.2 to 140)
0.1
Deg
I-14
External Defrost
0 (Off), 1 (On)
I-16
MOP
0 (Off), 1 (On)
I-19
Div Input
0 to 100
0.1
%
I-20
Rem Evap Temp
-49 to 128 (-56.2 to 262)
0.1
Deg
I-21
Remote Pressure
-3.4 to 180.0
0.1
Bar
I-25
Load Shedding
0 (Off), 1 (On)
O-05
Defrost Control
0 (Off), 1 (On)
O-07
Case Fans
0 (Off), 1 (On)
O-08
Light Relay
0 (Off), 1 (On)
O-09
EEV Opening
0 to 100
0.1
%
O-10
Last Def. Time
00:00 to 23:59
hh:mm
O-11
Last Def. Length
00:00 to 03:00
hh:mm
O-12
Last Def. Ctrl Temp.
-42 to 60 (-43.6 to 140)
0.1
hh:mm
O-13
Last Def. Type
0 (None), 1 (Internal),
2 (External), 3 (Network),
4 (Display), 5 (Timed)
O-15
Alarm Relay
0 (OK), 1 (Alarm)
O-20
Door Open Time
00:00 to 23:59
hh:mm
O-21
Door Open Length
00:00 to 03:00
hh:mm
O-30
Set Point Offset
-49 to 60 (-56.2 to 140)
0.1
Deg
O-32
Timer
0 (Off), 1 (On)
O-01
Thermostat
0 (Closed). 1 (Open)
O-18
Run Time
0 to 128
1
K Hrs
S-01
Control State
0 (Stabilise), 1 (Normal),
2 (Defrost Min), 3 (Defrost Max),
4 (Drain Down), 5 Fan Delay
6 (Recovery), 7 (OT Alarm),
8 (UT Alarm), 9 (Fans Only),
10 (Lights Only), 11 (Case Off),
12 (Pump Down), 13 (Defrost Hold)
14 (Load shedding)
S-02
Valve State
0 (Off). 1 (Start). 2 (Run). 3 (Problem).
4 (Fail). 5 (Shed)