P-95
Trap Stops LLV/Fans
0 (No). 1 (Yes0
1
0
0
P-99
Load Shedding
0 (Off). 1 (Mode 10. 2 (Mode 2)
1
0
0
P-35
Display Pin
0 – 999 (0 = off)
1
0
0
P-20
Alarm Delay
00:00 to 99:00
01:00
mm:ss
20:00
20:00
P-21
UT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
-30 (-22)
-2 (28.4)
P-22
OT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
-15 (5)
5 (41)
P-23
Log Probe Type
0 = Off. (Logging with no alarms)
1 = Logging (Probe Fault alarm only)
2 = Logging/Alarm (Prb Flt and OT/UT)
Off
Off
P-24
Slug Log Probe
0 = Off. 1 = On
Off
Off
P-25
Log Alarm Delay
00:00 to 99:00
01:00
mm:ss
20:00
20:00
P-26
Log UT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
-35 (-31)
-1 (30.2)
P-27
Log OT Alarm
-49 to 60 (-56.2 to 140)
0.1
Deg
-12 (10.4)
6 (42.8)
P-28
Buzzer Mode
0 = Off. 1 = On
On
On
P-40
Defrost Mode
0 (Local), 1 (Remote),
2 (External)
Local
Local
P-41
Defrost Start
00:00 to 23:59
00:01
hh:mm
01:00
01:00
P-42
Defrosts per Day
0 to 8
1
6
6
P-43
No Defrost Time
0 to 25
1
hours
12
12
P-44
Def Terminate
-42 to 30 (-43.6 to 86)
0.1
Deg
14 (57.2)
10 (50)
P-45
Def Min Time
00:00 to 99:00
01:00
mm:ss
05:00
05:00
P-46
Def Max Time
00:00 to 99:00
01:00
mm:ss
24:00
24:00
P-47
Drain Down
00:00 to 24:00
00:15
mm:ss
01:30
01:30
P-48
Recovery Time
00:00 to 99:00
01:00
mm:ss
30:00
30:00
P-89
Pump Down Time
00:00 to 99:00
01:00
mm:ss
00:00
00:00
P-86
Fan Delay mode
0 = Time
1 = Temp
1
0
0
P-49
Fan delay
00:00 to 99:00
01:00
mm:ss
03:00
03:00
P-88
Fan Delay Temp
-42 to 30 (-43.6 to 86)
0.1
Deg
-20 (-4)
0.0 (32)
P-50
Fans In Defrost
0 = Off. 1 = On
On
On
P-91
Defrost Type
0 (Elec). 1 (Elec/Cin)
1
0
0
P-94
Defrost Hold
0 = Off. 1 = On
Off
Off
P-86
Defrost Skip
0 (Off). 1(On)
1
0
0
P-97
Defrost Skip Time
00:00 to 99:00
01:00
mm:ss
12:00
12:00
P-80
Door alarm delay
00:00 to 99:00
01:00
mm:ss
20:00
20:00
P-81
Door Closes EEV
0 = No. 1 = Yes
No
No
P-82
Door Stops Fan
0 = No. 1 = Yes
No
No
P-60
Lights Mode
0 (Local), 1 (Remote)
Local
Local
P-61
Sun Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-62
Sun Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-63
Mon Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-64
Mon Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-65
Tue Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-66
Tue Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-67
Wed Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-68
Wed Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-69
Thu Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-70
Thu Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-71
Fri Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-72
Fri Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-73
Sat Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-74
Sat Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-30
Broadcast ID
0 to 999
1
0
0
P-31
Refrigerant
See Refrigerant Table Below
1
0
0
P-32
Pressure Units
0 (Absolute). 1 (Gauge)
1
1
1
P-33
Evap Offset
0.0 to 1,0
0.1
0.0
0.0
P-34
Glide
0.0 to 5.0
0.1
0.0
0.0
dFLt
Restore default settings
Refrigerant Table
0 = None. 1 = R12. 2 = R13. 3 = R13B1. 4 = R22. 5 = R23. 6 = R32. 7 = R114. 8 = R134A. 9 = R142B. 10 = R227. 11 = R401.
12 = R401A. 13 = R401B. 14 = R402. 15 = R402A. 16 = R402B. 17 = R404A. 18 = R407A. 19 = R407B. 20 = R407C. 21 = R500
22 = R502. 23 = R503. 24 = R507. 25 = R717. 26 = R290 (Propane). 27 = R744. 28 = R407F. 29 = R410A