User guide

Revision 7.1b Page 13 of 31
Mercury Coldroom Panel Installation Guide
www.resourcedm.com
Ensure that all power is
switched off before
installing or maintaining
this product
P-94
Defrost Hold
0 = Off. 1 = On
1
0
0
P-96
Defrost Skip
0 = Off. 1 = On
1
0
0
P-97
Defrost Skip Time
00:00 to 99:00
01:00
mm:ss
12:00
12:00
P-80
Door alarm dly
00:00 to 99:00
01:00
mm:ss
20:00
20:00
P-81
Door Closes LL
0 = No. 1 = Yes
1
No
No
P-82
Door Stops Fan
0 = No. 1 = Yes
1
No
No
P-60
Lights Mode
0 = Local. 1 = Remote
1
Local
Local
P-61
Sun Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-62
Sun Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-63
Mon Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-64
Mon Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-65
Tue Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-66
Tue Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-67
Wed Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-68
Wed Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-69
Thu Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-70
Thu Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-71
Fri Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-72
Fri Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-73
Sat Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-74
Sat Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
dFLt
Restore default values
*Note: Only PT1000 probes read up to +128 Degrees C
NTC probes read up to -49 to +60 degrees C
Parameter table for EEV Type
Number
Parameter
Range
o
C (
o
F )
Step
Units
Def. LT
o
C (
o
F )
Def. HT
o
C (
o
F )
P-01
Cut-in Temp
-42 to 30 (-43.6 to 86)
0.1
Deg
-20 (-4)
0.0 (32)
P-02
Diff
0 to 10 (0 to 18)
0.1
Deg
2 (3.6)
1.5 (2.7)
P-03
Control Weight
0 to 100
1
%
50
50
P-04
Display Weight
0 to 100
1
%
50
50
P-08
Superheat Ref
0 to 12 (0.0 to 21.6)
0.1
Deg
6 (10.8)
6 (10.8)
P-09
Response On
1 to 30
1
10
10
P-10
Response Off
1 to 30
1
10
10
P-11
Control Type
0 (EEV). 1 (EET). 2 (EEV/T)
1
0
0
P-17
Evap select
0 (Local). 1 (Rem 1).
2 (Rem 2). 3 (Rem 3)
1
0
0
P-51
EEV Min Opening
0 to 100
1
%
10
10
P-52
Superheat Problem
0.0 to 12.0
0.1
Deg
0.0
0.0
P-53
EEV Problem Opening
0 to 100
1
%
10
10
P-54
EEV Problem Time
00:00 to 99:00
01:00
mm:ss
03:00
03:00
P-56
EEV Start Opening
0 to 100
1
%
10
10
P-55
Ave Valve Opening
0 to 100
1
%
100
100
P-57
Div Value
0 to 100
1
%
50
50
P-85
Key-switch Mode
Not Used
-
-
-
P-87
Control Probe type
0 = Use Air on Probe
1 = Use Log Probe
1
0
0
P-90
Resistor Case Off
0 = Disabled. 1 = Enabled
0
0
P-92
Fans temperature mode
0 = Off
1 = Temperature
2 = Over-temperature
3 = Temp/OT
1
0
0
P-93
Fans Off Temperature
-42 to 30 (-43.6 to 86)
0.1
Deg
-10 (14)
8 (46.4)
P-83
Fan Control
0 (Off). 1 (Run). 2 (Pulse)
1
1
1
P-78
Fan Pulse On
00:00 to 99:00
01:00
05:00
05:00
P-79
Fan Pulse Off
00:00 to 99:00
01:00
30:00
30:00
P-77
Control Fail Valve
0 to 100
0.1
%
0.0
0.0
P-98
Control Fail On/Off
00:00 to 10:00
01:00
mm:ss
00:00
00:00
P-29
Probe 1 Operation
( Digital Input )
0 = Plant Fault
1 = External Defrost Input
1
0
0
P-18
Service Time
0 to 128
1
K Hrs
60
60