User guide
Revision 7.1b Page 13 of 31
Mercury Coldroom Panel Installation Guide
www.resourcedm.com
Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
P-94
Defrost Hold
0 = Off. 1 = On
1
0
0
P-96
Defrost Skip
0 = Off. 1 = On
1
0
0
P-97
Defrost Skip Time
00:00 to 99:00
01:00
mm:ss
12:00
12:00
P-80
Door alarm dly
00:00 to 99:00
01:00
mm:ss
20:00
20:00
P-81
Door Closes LL
0 = No. 1 = Yes
1
No
No
P-82
Door Stops Fan
0 = No. 1 = Yes
1
No
No
P-60
Lights Mode
0 = Local. 1 = Remote
1
Local
Local
P-61
Sun Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-62
Sun Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-63
Mon Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-64
Mon Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-65
Tue Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-66
Tue Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-67
Wed Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-68
Wed Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-69
Thu Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-70
Thu Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-71
Fri Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-72
Fri Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
P-73
Sat Lights On
00:00 to 23:59
00:01
hh:mm
08:00
08:00
P-74
Sat Lights Off
00:00 to 23:59
00:01
hh:mm
20:00
20:00
dFLt
Restore default values
*Note: Only PT1000 probes read up to +128 Degrees C
NTC probes read up to -49 to +60 degrees C
Parameter table for EEV Type
Number
Parameter
Range
o
C (
o
F )
Step
Units
Def. LT
o
C (
o
F )
Def. HT
o
C (
o
F )
P-01
Cut-in Temp
-42 to 30 (-43.6 to 86)
0.1
Deg
-20 (-4)
0.0 (32)
P-02
Diff
0 to 10 (0 to 18)
0.1
Deg
2 (3.6)
1.5 (2.7)
P-03
Control Weight
0 to 100
1
%
50
50
P-04
Display Weight
0 to 100
1
%
50
50
P-08
Superheat Ref
0 to 12 (0.0 to 21.6)
0.1
Deg
6 (10.8)
6 (10.8)
P-09
Response On
1 to 30
1
10
10
P-10
Response Off
1 to 30
1
10
10
P-11
Control Type
0 (EEV). 1 (EET). 2 (EEV/T)
1
0
0
P-17
Evap select
0 (Local). 1 (Rem 1).
2 (Rem 2). 3 (Rem 3)
1
0
0
P-51
EEV Min Opening
0 to 100
1
%
10
10
P-52
Superheat Problem
0.0 to 12.0
0.1
Deg
0.0
0.0
P-53
EEV Problem Opening
0 to 100
1
%
10
10
P-54
EEV Problem Time
00:00 to 99:00
01:00
mm:ss
03:00
03:00
P-56
EEV Start Opening
0 to 100
1
%
10
10
P-55
Ave Valve Opening
0 to 100
1
%
100
100
P-57
Div Value
0 to 100
1
%
50
50
P-85
Key-switch Mode
Not Used
-
-
-
P-87
Control Probe type
0 = Use Air on Probe
1 = Use Log Probe
1
0
0
P-90
Resistor Case Off
0 = Disabled. 1 = Enabled
0
0
P-92
Fans temperature mode
0 = Off
1 = Temperature
2 = Over-temperature
3 = Temp/OT
1
0
0
P-93
Fans Off Temperature
-42 to 30 (-43.6 to 86)
0.1
Deg
-10 (14)
8 (46.4)
P-83
Fan Control
0 (Off). 1 (Run). 2 (Pulse)
1
1
1
P-78
Fan Pulse On
00:00 to 99:00
01:00
05:00
05:00
P-79
Fan Pulse Off
00:00 to 99:00
01:00
30:00
30:00
P-77
Control Fail Valve
0 to 100
0.1
%
0.0
0.0
P-98
Control Fail On/Off
00:00 to 10:00
01:00
mm:ss
00:00
00:00
P-29
Probe 1 Operation
( Digital Input )
0 = Plant Fault
1 = External Defrost Input
1
0
0
P-18
Service Time
0 to 128
1
K Hrs
60
60