User guide

Revision 7.1b Page 10 of 31
Mercury Coldroom Panel Installation Guide
www.resourcedm.com
Ensure that all power is
switched off before
installing or maintaining
this product
Setting up the Panel
Access to the Panel can be achieved by the following methods: -
Through the front panel keypad
Direct access by PC or palm top into the RS232 comms port. This requires a software package (Communicator) available on
the RDM website
Direct access by PC using Ethernet (IP-L) and an IP browser (e.g. Internet Explorer)
Through legacy front end panels on 485 networks
Through the RDM Data Manager.
Setup through the keypad
To enter setup mode, hold the Enter and Down buttons together for approximately 3 seconds until the message “Ent” appears on the
display. Now press the Enter button again to enter the function menu. IO will be displayed. Scroll up or down to go through the list.
Setup Function Menu
(Common to all types)
Display
Option
Explained in Paragraph
IO
View Inputs / Outputs and States
Input / output table
PArA
Set/View Parameters
Set view parameters
Unit
Probe type and Celsius/Fahrenheit option
Set View Unit
diSP
Display whole units or decimal
Display
tyPE
Set/View Controller Type
Set/view controller type
rtc
Set/view Clock (rtc = Real Time Clock)
Real Time Clock
nEt
Set/view network configuration
Network Configuration
SoFt
View software version
FANS
Toggle Fans Only mode
Fans
CASE
Toggle Case Off mode
Case Off
Ligt
Toggle Lights Only mode
Lights
OFSt
Probe Offset
Probe Offset
ESC
Exit Setup mode
Pin Menu Access
The configuration menus within the controller can be pin-protected (excluding “IO” and “Soft”). I.e. trying to access the settings on the
controller’s display will prompt the user for a pin number (p-35 on the parameters list). When enabled, if trying to access a menu within
the above table, the display will show ‘Pin’. Pressing the Enter button at this point will allow you to enter a 3 digit pin, allowing access to
the menus. The pin number can be set up through p-35 on the controller parameter’s page, either through the display or Data Manager.
NB if the pin has been lost then RDM technical can be contacted to retrieve it.