Install Instructions
Table Of Contents
VR8204A,M INTERMITTENT PILOT COMBINATION GAS CONTROL
69-0423—04 4
Fig. 5. Proper use of wrench on gas control with and without adapters.
Connect Pilot Gas Tubing
1. Cut tubing to desired length and bend as necessary
for routing to pilot burner. Do not make sharp
bends or deform the tubing. Do not bend tubing at
control after compression nut has been tightened,
as this may result in gas leakage at the connection.
2. Square off and remove burrs from end of tubing.
3. Unscrew brass compression fitting from the pilot
outlet (Fig. 4). Slip the fitting over the tubing and
slide out of the way.
NOTE: When replacing a control, cut off old compres-
sion fitting and replace with the compression
fitting provided on the combination gas control.
Never use the old compression fitting as it may
not provide a gas-tight seal. Refer to Fig. 6.
Fig. 6. Always use new compression fittings.
4. Push tubing into the pilot gas tapping on the outlet
end of the control until it bottoms. While holding
tubing all the way in, slide fitting into place and
engage threads—turn until finger tight. Then
tighten one more turn with wrench. Do not over-
tighten.
5. Connect other end of tubing to pilot burner accord-
ing to pilot burner manufacturer’s instructions.
WIRING
Follow the wiring instructions furnished by the appliance
manufacturer, if available, or use the general instructions
provided below. Where these instructions differ from the
appliance manufacturer, follow the appliance
manufacturer instructions.
All wiring must comply with applicable electrical codes
and ordinances.
Disconnect power supply before making wiring
connections to prevent electrical shock or equipment
damage.
1. Check the power supply rating on the gas control
and make sure it matches the available supply.
Install thermostat and other controls as required.
2. Connect control circuit to gas control terminals.
See Fig. 5 and 7.
APPLY WRENCH
FROM TOP OR
BOTTOM OF GAS
CONTROL TO
EITHER SHADED AREA
WHEN FLANGE IS NOT USED
APPLY WRENCH
TO FLANGE ONLY
WHEN FLANGE IS USED
M2914A
GAS CONTROL
TIGHTEN NUT ONE TURN
BEYOND FINGER-TIGHT.
TO PILOT
BURNER
FITTING BREAKS OFF AND CLINCHES
TUBING AS NUT IS TIGHTENED.
M3076B