R8182D,H COMBINATION PROTECTORELAY™ PRIMARY CONTROL AND AQUASTAT
®
CONTROLLER
69-0599—2 4
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or equipment
damage.
Disconnect power supply before wiring to prevent
electrical shock or equipment damage.
All wiring must comply with local codes, regulations, and
ordinances.
Follow the wiring instructions furnished by the appliance
manufacturer, if available, or see Fig. 6 through 9. For
wiring multiple zoning systems, see Fig. 8 and 9.
The R8182 is equipped with special wiring terminals.
Wires can be wrapped around the terminal screw or
inserted from side.
Method 1
1. Strip 7/16 in. of insulation from
wire end.
2. Wrap wire 3/4 of distance
around screw as shown.
3. Using a standard, flat-head
screwdriver, tighten screw until
wire is snugly contacting screw
and contact plate.
4. Tighten screw an additional half turn.
Method 2
1. Strip 5/16 in. of insulation from
wire end.
2. Insert wire beneath screw as
shown.
3. Follow steps 3 and 4 in Method
1.
NOTE: Do not use a push-type
ratchet screwdriver.
The TRADELINE® R8182D,H can be converted to
replace an R8182B,C,E,F or a White Rodgers 6C92-2 or
6C92-3. When replacing a White Rodgers model, the
immersion well must also be replaced. See Fig.5 for
Aquastat limit connections necessary for each R8182D,H
conversion.
To release the wires from the R8182, insert a screwdriver
into the rectangular hole adjacent to the wire, push
inward to release the locking-grip on the wire, and pull
the wire out of the terminal hole.
To reinsert the wire into a new terminal hole, simply push
the wire into the new slot.
Fig. 6. Converting R8182D,H to replace other controls.
M8843
M4516
A
M4526
USING THE TRADELINE® R8182D
TO REPLACE R8182F:
1. REMOVE BLUE WIRE FROM
THIS TERMINAL AND INSULATE
END TO PREVENT CONTACT.
2. REMOVE OTHER BLUE WIRE
FROM THIS TERMINAL AND
CONNECT AS SHOWN BELOW.
3. CONNECT CIRCULATOR TO
ZC AND C2.
USING THE TRADELINE® R8182D
TO REPLACE R8182B,E OR
WHITE RODGERS 6C92:
1. REMOVE WHITE ABD BLACK
LEADS FROM THEIR TERMINAL
AND CONNECT WITH A
SODDERLESS CONNECTOR.
TO USE TRADELINE® R8182H
TO REPLACE R8182J:
1. REMOVE RED AND WHITE
LEADS FROM THEIR TERMINALS
AND CONNECT WITH A
SOLDERLESS CONNECTOR.
COMPLETED WIRING
TO REPLACE
R8182B,E AND
WHITE RODGERS 6C92
COMPLETED
WIRING TO
REPLACE
R8182C,F
L
O
H
I
BLUE
WHITE
BLACK
YELLOW
L
O
H
I
BLUEBLUE
BLACK
OR RED
YELLOW