HONEYWELL AQUAPUMP 3-SPEED CIRCULATION PUMPS
5 62-0383EFS—05
PUMP REPLACEMENT
Use this cross-reference tool to meet your installation needs.
Table 4. Cross Reference for Pump Replacement
The information in this table is based on publicly available information as of the date of this publication. Honeywell is not liable if
information is found to be incorrect.
If the cross-referenced model uses a flow check valve, then use a flow check with the Honeywell model as well.
TROUBLESHOOTING
Honeywell Grundfos Taco
Bell &
Gossett Armstrong Wilo
Model Pump
Length
Speed Single
Speed
3-Speed Single
Speed
3-Speed Single
Speed
3-Speed
PC3F1558IUF00 6.5”
High UP-42F
UP-42F-FC
UPS15-58 High
UPS15-58-FC High
005F
007F
008F
008F-IFC
00R High
00R Med
NRF-22
LR-20WR
Astro 30
Astro 30-3
Astro 50-3
Astro 230C1
Star 16 Star S16 High
Medium UP15-42FC UPS15-58 Low
UPS15-58-FC Low
005F-IFC
006F
006F-IFC
007F-IFC
00R Low NRF9F/LW
NRF-25 Med
Star S16 Med
Low UP15-18F
UP15-18F-FC
Star 5
S16 Low
PC3F2699IUF00 6.5”
High UP26-96F
UP26-96F-FC
UP26-116F
UP26-116F-FC
UPS26-99 High
UPS26-99-FC High
0011F
0011F-IFC
0013F
0013F-IFC
NRF-36 Med
NRF-45 Med
H-41
E7
Astro 50
Astro 50-3
Star 30F
Star 32F
S21 High
Medium UP26-64F
UP26-99FC
UPS26-99 Low
UPS26-99-FC Low
0014F
0014F-IFC
Star 17 FX S21 Med
Low NRF-33 Star S21 Low
PC3F4344IUF00 8.5”
High UP43-44F
UP43-44F-FC
UPS43-44 High
UPS43-44-FC High
HV
H-32
E16
Medium UPS43-44 Med
UPS43-44-FC Med
0010F
0012F-IFC
0010 Med NRF-33 H32
Low UPS43-44 Low
UPS43-44-FC Low
0010F-IFC 0010 Low
Fault Cause Action
Pump not running
No operating voltage Check the electrical system.
Rotor/shaft stuck • Isolate the pump from the power supply.
• Remove the vent screw (see Fig. 9).
• Turn the shaft clockwise using a small screwdriver.
• Screw in the vent screw.
• Switch on the pump.
Squealing noise Air in the pump
• Verify that water is in the system and the service valves
are open.
• Verify that the pump is installed so that the motor shaft
is horizontal (Fig. 5).
• Bleed the pump
Loud noises [> 43 dB(A)] Pump flow too high Reduce the pump speed using the knob or button
Cavitation due to insufficient supply
pressure
• Check the operating pressure of the system.
• Verify that the circulator intake is near the expansion
tank. Relocate if necessary.
Pump is hot Normal It is normal for the pump to feel hot as the cast iron will get
about as hot as the water.