Install Instructions

HONEYWELL AQUAPUMP 3-SPEED CIRCULATION PUMPS
2 62-0383EFS—05
DESCRIPTION
Table 3. Electrical data
FLOW CURVES
Fig. 2. Flow curve for PC3F1558IUF00.
Fig. 3. Flow curve for PC3F2699IUF00.
Fig. 4. Flow curve for PC3F4344IUF00.
INSTALLATION
CAUTION
Voltage Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before beginning installation.
Read and understand the operating instructions before
working on the pump.
Only operate the pump if it is in perfect operating condition.
Only use it as intended; staying aware of safety and risks,
and adhering to the instructions in this manual.
Install the pump in a frost-free, dry, well ventilated area.
1. Pump location considerations
Locate the pump where there is sufficient room for
installation and service. It is a good practice to install
flanges and service valves (not included) on each side of
the pump to allow service without draining the system.
It is also good practice to install the circulator inlet as close
to the expansion tank outlet as is practical.
Do not place the pump at the lowest point in the piping
system as this is where dirt and sediment collect. Do not
place the pump at the highest point in the piping system,
either, as this is where air accumulates.
Table 1. Pump data by model
Pump Model
Max. Flow
Max. Pressure
Head
GPM LPM Feet Meters
PC3F1558IUF00 15 55.6 19.4 6
PC3F2699IUF00 34 92.7 31 9
PC3F4344IUF00 59 170 17 5.2
Table 2. Optional and Replacement Parts
Pump Model Check Valve Gasket
PC3F1558IUF00 PCV100 PCG100
PC3F2699IUF00 PCV125 PCG100
PC3F4344IUF00 PCV150 PCG150
Pump Model
Speed 1 Speed 2 Speed 3
Power
Cur-
rent Power
Cur-
rent Power
Cur-
rent
PC3F1558IUF00 32W 0.28A 55W 0.48A 85W 0.74A
PC3F2699IUF00 125W 1.09A 175W 1.52A 205W 1.78A
PC3F4344IUF00 145W 1.26A 185W 1.61A 210W 1.83A
PC3F1558IUF00
M32852A
2
2
4
6
8
10
10
0
0
4
6
8
12
12
14
14
16
18
20
16
18
1
22
WITHOUT CHECK VALVE
WITH CHECK VALVE
2
3
H
(FEET)
US GPM
M32833A
0
5
10
15
20
25
30
0 5 10 15 20 25 30 35
1
PC3F2699IUF00
WITHOUT CHECK VALVE
WITH CHECK VALVE
3
1
2
H
(FEET)
US GPM
PC3F4344IUF00
M32851A
H
(FEET)
US GPM
0
2
4
6
8
10
12
14
16
18
0 5 10 15 20 25 30 35 40 45 50 55 60 65
3
2
1
WITHOUT CHECK VALVE
WITH CHECK VALVE