Install Instructions

® U.S. Registered Trademark
Copyright © 2001 Honeywell • All Rights Reserved
INSTALLATION INSTRUCTIONS
95- 6701- 5
L6081A
Aquastat® Controller
APPLICATION
The L6081A is a triple function controller; it is used as a
high limit, low limit, and circulator control. This controller
is designed to replace the controls listed in Table 1.
When replacing some of these controls, only 1 or 2 of the
L6081A switching functions may be needed. Refer to Fig.
2 to determine which terminals are used in a given
application.
Table 1. Controls L6081A Replaces.
a
All require a 124904 Well Adapter to fit L6081A case to well (order separately, see form 68-0040, Wells and Fittings
for Temperature Controllers).
b
Well for L6081A must be added when replacing these models.
INSTALLATION
When Installing This Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Explosion Hazard.
Can cause serious injury, death or property
damage.
Use this product only in systems with pressure
relief valves.
WARNING
Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect power supply before installation to
prevent electrical shock or equipment damage.
NOTE: If new immersion well is needed, refer to form
68-0040 Wells and Fittings for Temperature
Controllers for ordering information.
Mounting
Follow the mounting system manufacturer instructions if
available; otherwise, proceed as follows:
1. Turn off power and drain the system if necessary.
2. Remove old control.
3. loosen the captive cover mounting screw on the
L6081A and pull off the cover.
Honeywell General Controls
a
Mercoid
a
Penn
a
White Rodgers
a
L401A
L4010B
L4062A
L4062B
L4081A,B
L6062A
L6081A,C
L52F
L52G
L52H
L52J
L52K
L52L
480
DA-36-153
443AT
b
4432
447G 4432X
4420 4433
4420X 4433X
4422 4436
4422X 4437
11A61
b
11C61
1131
b
1135
11C30
1115
11C31

Summary of content (4 pages)