Adjusting L6008G Interstage Differential
The L6008G Controller has an adjustable interstage
differential. The setpoint adjustment knob determines the
temperature at which the right switch operates. The left
switch can be adjusted to operate from 3° to 10°F (1.7° to
5.6°C) above the point of operation of the right switch. The
Interstage differential is adjusted by turning the star wheel
with a narrow screwdriver inserted into the rectangular
hole in the chassis. See Fig. 8
SELECT MODELS HAVE FOUR TERMINALS.
M8972
Fig. 8. Interstage differential adjustment on an L4008L
or L6008G.
RIGHT
SWITCH
LEFT SWITCH
STAR WHEEL (INTERSTAGE
DIFFERENTIAL ADJUSTMENT)
1
1
CHECKOUT
WARNING
CAN CAUSE PROPERTY DAMAGE, SEVERE
INJURY OR DEATH.
This product is intended for use only in systems
with a pressure relief valve.
Check to be sure the Aquastat® controller is properly
installed and adjusted. Put the system into operation and
observe the action of the control through several cycles to
make sure that it provides proper control of the system as
described in the Operation section. Make any additional
adjustments necessary to assure comfort requirements.