Cross Reference
23
FEATURES AND FUNCTIONS CROSS-REFERENCE
Universal
Service Part
Type
of Gas
Ignition
Source
Typical
Ignition
Hardware
Includes Honeywell White-Rodgers Robertshaw
Johnson
Controls
S8910U3000
Nat or LP
Switched
Line
Voltage
Norton 201,
Norton 271,
Hot Surface
Elements,
Q354 Flame
Rod
S89C1004, S89C1012,
S89C1046, S89C1087,
S89C1103, S89D1002,
S89G1005, S89G1013,
S89G1021, S89G1047,
S89H1003, S89H1011,
S89H1029, S89J1008,
S890C1007, S890D1006,
S890G1003, S890G1011,
S890G1029, S890G1037,
S890H1002, S890H1010,
S890H1028
50E47-1 thru 50E47-79,
50E47-101 thru 50E47-179,
50E47-201 thru 50E47-279,
50E47-301 thru 50E47-379,
50F47-1 thru 50F47-79,
50F47-101 thru 50F47-179,
50F47-201 thru 50F47-279,
50F47-301 thru 50F47-379
HS780-17NL-104A,
HS780-17NL-108A,
HS780-17NL-304A,
HS780-17NL-308A,
HS780-17NR-104A,
HS780-17NR-306A,
HS780-17NR-308A,
HS780-34NL-108A,
HS780-34NL-304A,
HS780-34NL-306A,
HS780-34NL-308A,
HS780-34NL-312A,
HS780-34NR-104A,
HS780-34NR-306A,
HS780-34NR-308A,
HS780-34NR-312A,
HS780-34PL-308A,
S8610U3009
Nat or LP Internal
Q345, Q3451,
Q3452
Integral
Damper
Connector
S86 Series ,S90 Series,
S8600 Series,
S8610 Series,
S8620 Series,
S8660 Series,
S8670 Series,
S8680 Series
50D49-350, 50D49-360,
50D49-361, 50D50-843,
50D49-401
780-002, 780-003,
780-715, 780-735,
780-736, 780-737,
780-845, SP715,
SP715A, SP735D,
SP735L, USI715U,
SP735, SP750 Series
CSA42, 43,
44, 45, 46, 48,
49, G60, G65,
G67, G770
Series
Y8610U6006
Nat or LP Internal
Adapter for
Pilot Burner
Included
VR8304M3558
gas valve
Y8610U3003
Y8610U4001
Nat or LP Internal
Adapter for
Pilot Burner
Included
VR8204A2142
gas valve
APPLICATIONS TIMINGS
Universal
Service Part
Ignition System
Flame
Sensor
Ignition
Sequence
(Note 1)
Ignition
Trials To
Lockout
(Note 1)
Ignition Trial
Time
Between Trial
Time
Pre-Purge
Flame
Failure
Response
Time
S8910U3000
Line Volt Hot
Surface Ignition
1 or 2 Rods P
1 or 3
Field Selectable
4 sec. or 7 sec.
Field Selectable
96 sec., 3 Trial
Mode Only
32 sec or less 1.5 sec.
S8610U3009
Intermittent Pilot 1 or 2 Rods C C
15 sec. or
90 sec.
Field Selectable
5 Minute Delay
After Failed Trial
for Ignition
0 sec. or 30 sec.
Field Selectable
2.0 sec. max.
Y8610U6006
Conversion for
Standing Pilot
Single Rod C C
15 sec. or
90 sec.
Field Selectable
5 Minute Delay
After Failed Trial
for Ignition
0 sec. 2.0 sec. max.
Y8610U4001
Conversion for
Standing Pilot
Single Rod C C
15 sec. or
90 sec.
Field Selectable
5 Minute Delay
After Failed Trial
for Ignition
0 sec. 2.0 sec. max.
Ignition Modules Selection Guide
For a complete cross-reference, visit www.customer.honeywell.com
Gas Controls