TROUBLESHOOTING
Table 2 provides a troubleshooting guide for the DS05 Dial Pressure Regulating Valve.
Table 2. Troubleshooting the DS05 Dial-Set Pressure Regulating Valve.
Problem Solution
Whistling noise. Slightly increase or decrease the outlet pressure until the noise goes away.
Will not hold pressure. Clean the filter cartridge as described in the installation section.
Chatters. Replace screen and O-rings.
Replace the cartridge as shown in Figure 3.
Freezes up. Replace bonnet or cartridge if damaged.
To avoid further freeze up:
Temporarily (slightly) open a downstream faucet if the DS05 will be exposed to
temperatures below 32° F (0° C). The slight water flow will eliminate freeze-up.
Move the DS05 to a location with an ambient temperature above 32° F (0° C) if it is
currently exposed to prolonged temperature below 32° F (0° C).
Pressure gauge measures a lower
pressure under flow conditions than was
originally set during static conditions.
DS05 is functioning properly. No action is necessary. The pressure decrease is
characteristic of all direct acting pressure regulating valves and is referred to as
falloff.