Installation Guide
DCN: 140-02338-01 DRAFT 20619
Page 16
Menu Mode Screen
Menu Mode options
SETUP User preference settings
SYSTEM Thermostat HVAC system settings
ZWAVE Z-Wave network install or remove
CLOCK Setting the thermostat time and day
INFO Displays thermostat version and setup info
SETUP Menu
User preference settings.
FAHRENHEIT OR CELSIUS. Select the temperature display mode.
BACKLIGHT TIMEOUT. Sets the time from last button press that the backlight will turn off.
Range:10-30 seconds. Note: long backlight timeouts will reduce battery life.
If the thermostat is powered from 24VAC, the backlight timeout can be set to “0” which will
keep the backlight on continuously.
SENSOR CALIBRATION Change the temperature calibration by +/- 7 degrees.
Use the Up/Dn arrow buttons to change to the desired display temperature.
SYSTEM Menu
SYSTEM TYPE. Select the system type, STANDARD or HEAT PUMP
FAN TYPE (Standard systems only).
Select fan type: GAS (typical default setting) or ELECTRIC
CHANGE OVER TYPE (Heat Pump systems only).
Select the Changeover type:
Changeover WITH COOL (typical default setting)
Changeover WITH HEAT
Use the
UP/DOWN
buttons to select
the desired menu
item
Press “Select”
to go to the
selected menu
item screen
Press “Done” to
go back to the
Thermostat
Main Screen
Menu item display