User's Manual

RS1 Type Range: A curve, Type 2, Type 3 Default: Type 3
RS2 Type Range: A curve, Type 2, Type 3 Default: Type 3
RS2 Location Range: IN (indoors), OUT (outdoors) Default: IN
R1 Node ID ID for a Z-Wave remote sensor Default: 0
R2 Node ID ID for a Z-Wave remote sensor Default: 0
Humidity Settings: Submenu for humidity settings
RH Display Range: Off or On Default: On
Turns on or off the RH display on the main thermostat screen.
RH Setpoint Range: 20 to 80 in 5% steps Default: 55%
Sets the RH setpoint for Humidity control functions.
RH Setpoint Away Range: 20 to 80 in 5% steps Default: 65%
Sets the RH setpoint when in the AWAY mode.
RH Temp Delta Range: 1 to 5 deg Default: 2 deg
Sets the maximum overcooling temperature allowed for humidity control.
RH Setpoint Delta Range: 1 to 10 % Default: 5 %
Sets the % above the RH setpoint that the Humidity control will be activated.
RH On Time Range: 0 to 60 minutes Default: 30 min
Sets the maximum runtime for Humidity control to try to correct RH level.
RH Off Time Range: 0 to 60 minutes Default: 30 min
Sets the minimum off time for Humidity control after On time expires.
RH Off Delta Range: 0 to 10 % Default: 2%
Sets the % RH below the RH setpoint that the Humidity control will lower the room RH to before turning off.
Relay Setup (for aux relay A1 output)
A1 Relay mode Range: see below Default: Off
Off. No relay function
Humidify: Relay turns on when RH is below humidity setpoint
Dehumidify: Relay turns on when RH is above humidity setpoint
Net: Z-Wave commands turn Relay On and Off.
Configuration parameter #95 See Z-Wave Command Summary
Vent: Relay turns on when Vent is active.
DH-Fan: HVAC system fan speed control during dehumidification.
A1 Fan Interlock Range: Off, On Default: Off
Turns on fan output (G) when relay A1 is on
Restore Defaults Range: Yes, No Default: No
Restores all settings to factory defaults.
Press Yes to restore defaults
Press No to exit and not restore defaults