Rover Protections 
Protection 
Behavior 
PV Array Short 
Circuit 
When PV shot circuit occurs, the controller will stop charging. 
Clear it to resume normal operation 
PV Overvoltage 
If the PV voltage is larger than maximum input open voltage 
100VDC, PV will remain disconnected until the voltage drops 
below 100VDC. 
PV Overcurrent 
The controller will limit the battery charging  current to the 
maximum battery current rating. Therefore, an over-sized solar 
array will not operate at peak power. 
Load Overload 
If the current exceeds the maximum load current rating 1.05 
times, the controller will disconnect the load. Overloading must 
be cleared up by reducing the load and restarting the controller. 
Load Short Circuit 
Fully protected against the load wiring short-circuit. Once the 
load short (more than quadruple rate current), the load short 
protection  will  start  automatically.  After  5  automatic  load 
reconnect attempts, the faults must be cleared by restarting the 
controller. 
PV Reverse Polarity 
The controller will not operate if the PV wires are switched. Wire 
them correctly to resume normal controller operation. 
Battery Reverse 
Polarity 
The controller will not operate if the battery wires are switched. 
Wire them correctly to resume normal controller operation. 
Over-Temperature 
If the temperature of the controller heat sink exceeds 65
O
C, the 
controller will  automatically start  the  reducing the charging 
current and shut down when temperature exceeds 80
O
C 